Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop R
Sequence Number 8
Notes
Date Text
2003-11-05 00:00:00RESTAMP DENIED
  
 1) PLANS ARE REQUIRED TO BE SIGNED,
 SEALED AND DATED BY THE ARCHITECT.
  
 2) SHEET A3 DOES NOT SPECIFY THE CORRECT
 UL NUMBER FOR THE ONE HOUR STEEL COLUMN
 ASSEMBLY.
  
 3) TWO OF THE DETAILS ON S5 ARE NUMBERED
 INCORRECTLY.
  
 IN ORDER TO RESTAMP PLANS THEY MUST
 MATCH THE APPROVED PLANS ON FILE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714