| Plan Review Notes For Permit 02101307 |
| Permit Number |
02101307 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2004-10-28 00:00:00 | PROVISO: | | | AS PER 1ST REVIEW - | | | 1.PLAN SHEET M.3 FLEXIBLE DUCT | | | CONNECTION DETAIL, THIS DETIAL DOES NOT | | | INDICATE OR REFERENCE THE REQUIREMENT | | | FOR A FIRE DAMPER THAT IS DETAILED ON | | | PLAN SHEET A.5. | | | | | | 2.PLAN STILL DOES NOT INDICATE TOILET | | | EXHAUST TERMINATIONS AS SCREENED.THIS | | | IS REQUIRED ON EXHAUST WITH THE | | | EXCEPTION BEING FOR THE DRYER AND HOOD | | | EXHAUST.2001 FBC(M) 401.6, 504.4 & | | | 505.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|