Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop E
Sequence Number 7
Notes
Date Text
2005-09-30 00:00:00****** UNSAT ******
  
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULES.
 PLEASE SEE PANEL "A" IS SHOWN FEEDING
 BOTH SUB PANELS, HOWEVER RISER INDICATES
 ONE SUB PANEL FROM "A" AND ONE FROM
 "B"??
  
  
 2)NOTE: PLEASE SEE TWO NEW MAIN
 DISCONNECTS ADDED TO RISER.
 PLEASE SUBMIT AIC RATINGS FOR NEW MAINS
 PER 110.9, 215.5
 PLEASE NOW SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS "A" AND "B".
 250.110, 250.24, 250.122
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]