| Plan Review Notes For Permit 02101307 |
| Permit Number |
02101307 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2005-09-30 00:00:00 | ****** UNSAT ****** | | | | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | WITH PANEL SCHEDULES. | | | PLEASE SEE PANEL "A" IS SHOWN FEEDING | | | BOTH SUB PANELS, HOWEVER RISER INDICATES | | | ONE SUB PANEL FROM "A" AND ONE FROM | | | "B"?? | | | | | | | | | 2)NOTE: PLEASE SEE TWO NEW MAIN | | | DISCONNECTS ADDED TO RISER. | | | PLEASE SUBMIT AIC RATINGS FOR NEW MAINS | | | PER 110.9, 215.5 | | | PLEASE NOW SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM MAINS TO | | | PANELS "A" AND "B". | | | 250.110, 250.24, 250.122 | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] |
|