Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop R
Sequence Number 6
Notes
Date Text
2003-10-01 00:00:00REVISION DENIED
  
 1) ON SHEET S3 DETAILS 1 AND 2 HAVE BEEN
 ADDED, BUT ARE NOT CLOUDED. THE TYPICAL
 CONNECTOR DETAIL HAS BEEN REMOVED.
  
 2) ON S5 THE ADDED DETAILS AND ELEVATION
 CHANGE ARE NOT CLOUDED. DETAIL TAGS FOR
 1 AND 2 ON S5 ARE USED TWICE. PLEASE
 CORRECT TO AVOID CONFUSION.
  
 3) THE LOCATIONS FOR BALCONY SECTIONS 1
 AND 2 ON S3 ARE NOT INDICATED ON THE
 FLOOR PLANS. THEY ARE NOT CLOUDED.
  
 4) A REVISED SHEET S2 FOR THE ROOF AND
 3RD FLOOR PLAN WAS NOT SUBMITTED.
  
 5) A REVISED SHEET A5 WITH THE NEW
 ELEVATIONS SHOULD BE SUBMITTED.
  
 6) REVISED SHEET A3 SPECIFIES UL DESIGN
 X637 FOR THE STEEL COLUMNS. THIS DESIGN
 IS FOR ROUND PIPE COLUMNS. THE PLANS
 SPECIFY TUBE COLUMNS. PLEASE SPECIFY AN
 APPROPRIATE UL SYSTEM TO ACHIEVE THE ONE
 HOUR FIRE RATING.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS. ROOFING WAS NOT PART
 OF THE ORIGINAL PERMIT, BUT WAS ADDED
 WHEN CONTRACTOR WAS CHANGED.
  
 8) THE REVISED ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER OR HIS AGENT.
  
 IF YOU HAVE QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714