2003-07-28 00:00:00REVISION DENIED BY BUILDING
  
 1) SHEET A2 SPECIFIES 10-3/4" STAIR
 TREADS AND SECTION A ON A6 SPECIFIES
 10-1/2" TREADS. PLEASE CORRECT. MUST
 COMPLY WITH FBC 1007.3(1), THE SUM OF
 TWO RISERS AND A TREAD EXCLUSIVE OF THE
 NOSING SHALL BE NOT LESS THAN 24" NOR
 MORE THAN 25".
  
 2) SUBMIT REVISED ENERGY CALCULATIONS
 WHICH INCLUDE THE ADDITIONAL AREA AND
 GLAZED AREA.
  
 3) SHEET A3 APPEARS TO HAVE A TYPO AT
 THE DUMD WAITER. THE PLAN HAS DUMP WATER
 PLEASE CORRECT.
  
 4) THE OPENINGS IN THE NORTH WALL OF THE
 STAIRWELL THAT IS 17'-3" FROM THE
 PROPERTY LINE EXCEEDS 40% OF WALL AREA
 ALLOWED AS OPENINGS BY TABLE 600. PLEASE
 CORRECT.
  
 5) SPECIFY THE HEIGHT, ATTACHMENTS, AND
 COMPLIANCE WITH FBC 2405.5 FOR THE GLASS
 GUARDRAIL AT THE THIRD FLOOR BALCONY ON
 THE WEST ELEVATION. SUBMIT CALCULATIONS
 AND SHOP DRAWINGS AT THIS TIME OR APPLY
 UNDER SEPARATE PERMIT.
  
 6) THE EXTERIOR DOOR TO THE PANTRY DOES
 NOT HAVE AN ID TAG ON SHEET A2.
  
 7) THE NEW EXTERIOR DOOR TO THE PANTRY
 IS NOT CLOUDED ON S1.
  
 8) THE INTERNAL PRESSURE COEFFICIENT IS
 NOT INDICATED AS + OR - ON S3. PLEASE
 CORRECT.
  
 9)CORRECT THE FONT ON TYPICAL SC1 DETAIL
 ON S4, IT IS DIFFICULT TO READ.
  
 10) THE ROOF ELEVATIONS ON A5 AND S5 DO
 NOT CORRESPOND. PLEASE CORRECT.
  