| 2003-07-28 00:00:00 | REVISION DENIED BY BUILDING |
| | |
| | 1) SHEET A2 SPECIFIES 10-3/4" STAIR |
| | TREADS AND SECTION A ON A6 SPECIFIES |
| | 10-1/2" TREADS. PLEASE CORRECT. MUST |
| | COMPLY WITH FBC 1007.3(1), THE SUM OF |
| | TWO RISERS AND A TREAD EXCLUSIVE OF THE |
| | NOSING SHALL BE NOT LESS THAN 24" NOR |
| | MORE THAN 25". |
| | |
| | 2) SUBMIT REVISED ENERGY CALCULATIONS |
| | WHICH INCLUDE THE ADDITIONAL AREA AND |
| | GLAZED AREA. |
| | |
| | 3) SHEET A3 APPEARS TO HAVE A TYPO AT |
| | THE DUMD WAITER. THE PLAN HAS DUMP WATER |
| | PLEASE CORRECT. |
| | |
| | 4) THE OPENINGS IN THE NORTH WALL OF THE |
| | STAIRWELL THAT IS 17'-3" FROM THE |
| | PROPERTY LINE EXCEEDS 40% OF WALL AREA |
| | ALLOWED AS OPENINGS BY TABLE 600. PLEASE |
| | CORRECT. |
| | |
| | 5) SPECIFY THE HEIGHT, ATTACHMENTS, AND |
| | COMPLIANCE WITH FBC 2405.5 FOR THE GLASS |
| | GUARDRAIL AT THE THIRD FLOOR BALCONY ON |
| | THE WEST ELEVATION. SUBMIT CALCULATIONS |
| | AND SHOP DRAWINGS AT THIS TIME OR APPLY |
| | UNDER SEPARATE PERMIT. |
| | |
| | 6) THE EXTERIOR DOOR TO THE PANTRY DOES |
| | NOT HAVE AN ID TAG ON SHEET A2. |
| | |
| | 7) THE NEW EXTERIOR DOOR TO THE PANTRY |
| | IS NOT CLOUDED ON S1. |
| | |
| | 8) THE INTERNAL PRESSURE COEFFICIENT IS |
| | NOT INDICATED AS + OR - ON S3. PLEASE |
| | CORRECT. |
| | |
| | 9)CORRECT THE FONT ON TYPICAL SC1 DETAIL |
| | ON S4, IT IS DIFFICULT TO READ. |
| | |
| | 10) THE ROOF ELEVATIONS ON A5 AND S5 DO |
| | NOT CORRESPOND. PLEASE CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |