| 2003-10-20 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE THAT ONE SET OF PLANS | | | HAVE COME FOR A RE-STAMP, YET PLANS | | | HAS CHANGES ON PLANS, THEREFORE MAKING' | | | THESE "REVISIONS". | | | PLEASE SEE THAT ONLY ONE SET WAS SUB- | | | -MITTED FOR STAMPING AND TWO SETS REQ'D | | | DUE TO REVISIONS. | | | | | | 2)NOTE: PLEASE ALSO SEE PLANS NEED TO BE | | | SIGNED, DATED AND SEALED BY THE ARCH OF | | | RECORD. FAC 61G1-16.004, FS 481.221. | | | | | | 3)NOTE: PLEASE SEE RISER, LAST REV | | | CONTAINED CONDUCTOR SIZE FROM GUTTTER | | | TO DISC FOR ELEVATOR. PLEASE SEE THIS IS | | | NOW MISSING.? PLEASE CORRECT.SEE 240.21 | | | FOR TAPPED CONDUCTORS. | | | 4)NOTE: PLEASE CLARIFY GFI RECEPT REQ'D | | | FOR A/C COND UNITS. 210.63 | | | | | | 5)NOTE: PLEASE SEE PLANS, HIGHLIGHTED | | | FOR RECEPTS MISSING PER 210.52. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. REVISIONS FEES ARE NOW DUE FOR | | | ELECTRICAL PLANS. PLEASE ALSO SEE NOTES | | | FROM OTHER REVIEWERS AND FEE THAT MAY | | | BE DUE FOR OTHER TRADES ALSO. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|