| Plan Review Notes For Permit 02101307 |
| Permit Number |
02101307 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-03-10 00:00:00 | BUILDING DENIED | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) SPECIFY THE LOCATIONS AND MATERIALS | | | USED FOR DRAFTSTOPPING THE FLOOR/CEILING | | | ASSEMBLIES PER FBC 2305.2.2. SINGLE | | | FAMILY DWELLINGS. IN FLOOR/CEILING | | | ASSEMBLIES SEPARATING USEABLE SPACES | | | INTO TWO OR MORE APPROXIMATE AREAS WITH | | | NO GREATER THAN 500 SQ FT. DRAFTSTOPPING | | | SHALL BE PROVIDED PARALLEL TO THE MAIN | | | FRAMING MEMBERS. | | | | | | 3) THE NEW SHEETS OF DRAWINGS DO NOT | | | HAVE THE EMBOSSED SEAL OF THE DESIGNER | | | OF RECORD. | | | | | | 4) THE TABLE OF DESIGN PRESSURES ON A6 | | | DOES NOT CORRESPOND WITH THE REST OF THE | | | PLANS FOR OPENING MARKS, PRESSURES, ETC. | | | NOTE: THE CITY OF WPB IS LOCATED IN A | | | 140 MPH WIND ZONE. | | | | | | 5)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR FIXED GLASS WINDOWS LARGER | | | THAN 50 SQ FT. THIS IS THE MAXIMUM SIZE | | | COVERED BY THE PRODUCT APPROVAL THAT WAS | | | SUBMITTED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|