Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop M
Sequence Number 3
Notes
Date Text
2003-03-06 00:00:00DENIED:
  
 PLEASE NOTE, ONE SET OF PLANS WERE
 INADVERTENTLY STAMPED.DENIED COMMENTS
 WERE ATTACHED TO THE RESUB APPLICATION.
  
 PLEASE ADDRESS THE FOLLOWING:
 PLAN SHEET A.1 NOTE INDICATES ONE HOUR
 PROTECTION W/UL DESIGN L521 THROUGHOUT.
  
 THE MECHANICAL PLANS DO NOT REFLECT THIS
 TYPE OF CONSTRUCTION.PLEASE PROVIDE
 INFORMATION ON THE PROTECTION FOR THE
 HVAC SYSTEMS.ITEMS #4 & 5 IN THE UL
 L521 LISTING, INDICATE UL CLASS 0 OR 1
 FOR THE DROPS.
  
 PLEASE REFLECT THE ASSEMBLY ON THE
 MECHANICAL PLANS.
  