| Plan Review Notes For Permit 02101307 |
| Permit Number |
02101307 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-07-31 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | AND PANELS. RISER SHOWS PANELS AS MCB | | | AND PANEL SHOWN AS MLO? | | | | | | 2)NOTE: PLEASE ALSO SEE LOAD CALCULATION | | | -S, PLEASE RECONFIGURE AND CLARIFY | | | SUB PANEL AND TOTAL LOAD ON SERVICE. | | | 500MCM ID GOOD FOR 380A'S PER 310-16. | | | PLEASE SEE THAT 310-15 B6 MAY BE USED | | | BUT STOPS AT 400MCM FOR A 400A SERVICE. | | | 460A SERV SHOWN. | | | PLEASE ALSO CLARIFY WHERE SUB PANEL, | | | PANEL SCHEDULE IS? | | | | | | 3)NOTE: PLEASE SUBMIT REVISED PLANS, IN | | | ORDER TO VERIFY SERVICE AND LOCATIONS | | | OF PANELS. | | | | | | 4)NOTE: PLEASE SHOW ALL REVISIONS WITH | | | CLOUDS AND TRIANGLES. | | | | | | 5)NOTE: PLEASE SEE MISSING CONDUCTOR | | | SIZES ON RISER FOR SUB PANEL FROM GUTTER | | | PER 240-21 . | | | | | | 6)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FOR ELEV MOTOR, | | | 250-110/250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|