Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop E
Sequence Number 3
Notes
Date Text
2003-07-31 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS. RISER SHOWS PANELS AS MCB
 AND PANEL SHOWN AS MLO?
  
 2)NOTE: PLEASE ALSO SEE LOAD CALCULATION
 -S, PLEASE RECONFIGURE AND CLARIFY
 SUB PANEL AND TOTAL LOAD ON SERVICE.
 500MCM ID GOOD FOR 380A'S PER 310-16.
 PLEASE SEE THAT 310-15 B6 MAY BE USED
 BUT STOPS AT 400MCM FOR A 400A SERVICE.
 460A SERV SHOWN.
 PLEASE ALSO CLARIFY WHERE SUB PANEL,
 PANEL SCHEDULE IS?
  
 3)NOTE: PLEASE SUBMIT REVISED PLANS, IN
 ORDER TO VERIFY SERVICE AND LOCATIONS
 OF PANELS.
  
 4)NOTE: PLEASE SHOW ALL REVISIONS WITH
 CLOUDS AND TRIANGLES.
  
 5)NOTE: PLEASE SEE MISSING CONDUCTOR
 SIZES ON RISER FOR SUB PANEL FROM GUTTER
 PER 240-21 .
  
 6)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FOR ELEV MOTOR,
 250-110/250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]