| 2003-01-29 00:00:00 | BUILDING DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | THIS INFORMATION IS REQUIRED TO BE ON |
| | THE SIGNED AND SEALED CONSTRUTION |
| | DRAWINGS. A PAPER STAPLED TO THE |
| | DRAWINGS IS NOT ACCEPTABLE. |
| | |
| | 4) SPECIFY THE LOCATIONS AND MATERIALS |
| | USED FOR DRAFTSTOPPING THE FLOOR/CEILING |
| | ASSEMBLIES PER FBC 2305.2.2. |
| | |
| | 5) THE STRUCTURE IS LOCATED IN AN "A5" |
| | FLOOD ZONE, AN ELEVATION CERTIFICATE |
| | WILL BE REQUIRED. INDICATE THE PROPOSED |
| | GROUND FLOOR FINISH ELEVATION BASED ON |
| | N.G.V.D., NOT MEAN SEA LEVEL. NOTE: THE |
| | CITY CODE REQUIRES THE LOWEST FLOOR TO |
| | BE A MINIMUM OF SIX INCHES ABOVE BASE |
| | FLOOD ELEVATION. |
| | |
| | 6) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | PROVIDE A SOIL TEST REPORT FROM A |
| | SOIL ENGINEER. PROVIDE SUBSURFACE SOIL |
| | INVESTIGATION COMPLETE WITH SOIL BORINGS |
| | AND RECOMMENDATIONS. |
| | |
| | 7) STAIRS DO NOT COMPLY WITH FBC 1007.3 |
| | SEE STAIR SECTION A ON A6, WHICH THE |
| | SUM OF TWO RISERS AND A TREAD (EXCLUSIVE |
| | OF THE NOSING) IS 23.75". INDICATE THE |
| | DIMENSIONS OF THE HANDRAIL ON THE PLANS. |
| | SEE FBC 1007.5.3. |
| | |
| | 8) CANOPY WILL REQUIRE A SEPARATE PERMIT |
| | AS INDICATED ON THE PLANS. |
| | |
| | 9) BALCONY GUARDRAILS WILL REQUIRE A |
| | SEPERATE PERMIT AS INDICATED ON THE |
| | PLANS. |
| | |
| | 10) INDICATE ON THE PLANS THAT THE WIRE |
| | MESH IN THE SLAB WILL BE SUPPORTED BY |
| | APPROVED MATERIALS OR SUPPORTS AT |
| | SPACINGS NOT TO EXCEED THREE FEET. SEE |
| | FBC 1909.3. |
| | |
| | 11) SPECIFY THE CONNECTORS AND UPLIFTS |
| | FOR THE GIRDER TRUSSES INDICATED ON THE |
| | ROOF PLAN. |
| | |
| | 12) SPECIFY HOW THE REQUIRED ONE HOUR |
| | FIRE PROTECTION WILL BE PROVIDED FOR THE |
| | STEEL COLUMNS. |
| | |
| | 13) SHEET S2 SHOWS A 4" COLUMN ON THE |
| | THIRD FLOOR BETWEEN TWO SLIDING GLASS |
| | DOORS WITH A WOOD GIRDER TRUSS ABOVE AND |
| | BELOW. PROVIDE DETAILS INDICATING THE |
| | ATTACHMENT AT THE BASE AND CAP, COLUMN |
| | TYPE, FIRE PROTECTION, ETC. |
| | |
| | 14) PROVIDE A COVER SHEET FOR THE SHEAR |
| | WALL CALCULATIONS. PROVIDE THE TITLE |
| | BLOCK FOR THE ENGINEER (AND PHONE #), |
| | THE DESIGN CRITERIA THE CALCULATIONS ARE |
| | BASED ON, THE ADDRESS OF THE JOB, THE |
| | CONCLUSIONS THAT WERE REACHED. |
| | |
| | 15) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SLIDING GLASS DOORS WIDER THAN 8 FEET |
| | - SINGLE HUNG WINDOWS |
| | - FIXED GLASS WINDOWS WHICH INCLUDE |
| | RECTANGULAR SHAPES UP TO 58 SQ.FT. |
| | |
| | 16) THE NOTE ON A6 STATES THAT |
| | HURRICANE SHUTTERS ARE REQUIRED, HOWEVER |
| | NO STORM PANEL INFORMATION WAS SUBMITTED |
| | THE PRODUCT APPROVALS SUBMITTED ARE FOR |
| | IMPACT RESISTANT OR NON-IMPACT RESISTANT |
| | GLASS. PLEASE CLARIFY. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |