| 2003-01-21 00:00:00 | PLAN SHEET A.1 NOTE INDICATES ONE HOUR | | | PROTECTION W/UL DESIGN L 521 THROUGHOUT. | | | | | | THE MECHANICAL PLANS DO NOT REFLECT THIS | | | TYPE OF CONSTRUCTION.PLEASE PROVIDE | | | INFORMATION ON THE PROTECTION FOR THE | | | HVAC SYSTEMS. ITEMS #4 & 5 IN THE UL L | | | 521 INDICATE UL CLASS 0 OR 1 FOR THE | | | DUCTWORK & CEILING DAMPERS REQUIRED FOR | | | THE DROPS. | | | | | | PLEASE CLARIFY THE ASSEMBLY ON THE | | | MECHANICAL PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|