Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop M
Sequence Number 2
Notes
Date Text
2003-01-21 00:00:00PLAN SHEET A.1 NOTE INDICATES ONE HOUR
 PROTECTION W/UL DESIGN L 521 THROUGHOUT.
  
 THE MECHANICAL PLANS DO NOT REFLECT THIS
 TYPE OF CONSTRUCTION.PLEASE PROVIDE
 INFORMATION ON THE PROTECTION FOR THE
 HVAC SYSTEMS. ITEMS #4 & 5 IN THE UL L
 521 INDICATE UL CLASS 0 OR 1 FOR THE
 DUCTWORK & CEILING DAMPERS REQUIRED FOR
 THE DROPS.
  
 PLEASE CLARIFY THE ASSEMBLY ON THE
 MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.