Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop E
Sequence Number 10
Notes
Date Text
2006-02-07 00:00:00******* UNSAT ******
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SEE NOTE # 4 FROM
 PREVIOUS REVIEW. PLEASE INDICATE THE KW
 RATINGS FOR POOL HEATERS.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 FIGURED AT 125%, POOL PUMP(S), POOL
 HEATER(S).
 PLEASE SEE LOAD SHOWN ON POOL PANEL IS
 ALREADY SHOWN AT 96A'S WHICH IS OF
 CONCERN WITH THE ADDED LOADS FROM
 ORIGINAL PLANS.
  
  
 2)NOTE: PLEASE INDICATE ALL THE KW
 RATINGS FOR A/C EITH CU'S OR AHU'S
 WHICHEVER LOAD IS GREATER.
 THE LOADS SHOWN ON THE PANEL SCHEDULE(S)
 MENTIONS THE LOADS ALREADY @65%, HOWEVER
 EACH AHU SEEMS TO BE ABOUT 5KW OR SO,
 WHICH @65% WOULD NOT BE THE LOADS SHOWN.
 215.5
  
 3)NOTE: PLEASE SEE ALL SUB PANELS ARE
 NOW INDICATED AS "GARAGE PANELS"?
 PLEASE CORRELATE THE IDENTIFICATION WITH
 RISER.
  
 4)NOTE: PLEASE SEE RISER NOW SHOWS A
 DISCONNECTING MEANS AHEAD OF THE GARAGE
 PANEL "E', YET PLANS DO NOT SHOW THIS
 DISCONNECT. PLEASE ALSO SEE RISER WHICH
 SHOWS A MCB IN PANEL AT GARAGE?
 PLEASE CORRLELATE.
 PLEASE SEE THE EQUIPMENT GROUNDING
 CONDUCTOR FROM PANEL "C" IN MAIN HOUSE
 IS NOW MISSING TO THE GARAGE PANEL "E".
 PLEASE SEE 250.32.
 AN EQUIPMENT GROUNDING CONDUCTOR IS
 REQUIRED; THE ONLY EXCEPTION IS IF THERE
 ARE COMPLETELY NO OTHER METAL PARTS
 CONNECTED BETWEEN BLDGS. THIS WOULD BE ,
 WATER PIPES, CATV, PHONE ETC.
 THE CHANCES OF THERE BEING NO METALS
 PATHS OR FUTURE PHONE ETCIS VERY
 UNLIKELY.
 PLEASE INCLUDE THE EQUIPMENT GROUND AS
 SHOWN ON PREVIOUS PLANS.
  
 5)NOTE: PLEASE SEE LOAD CALCUALTIONS
 PROVIDE DO NOT PROVIDE ENOUGH
 INFORMATION FOR REVIEW OF MINS'
 REQUIRED. PLEASE EITHER SHOW A BREAK
 DOWN OR INDICATE THE VA/KW ON PANEL
 SCHEDULES. ( SMALL APPL, LAUNDRY/WASHER,
 DRYER ETC ETC.
 220,215.5
  
 NEW NOTE:
  
 6)NOTE: PLEASE SEE GARAGE SHOWS A 220V
 RECEPT, HOWEVER THIS IS NOT ON PANEL
 SCHEDULE FOR GARAGE.
 215.5
  
 ** PLEASE KNOW, THIS OFFICE IS UNABLE TO
 VERIFY CORRECT OCP AND AWG FOR SOME
 CIRCUITS AS LOADS ARE NOT SHOWN OR GIVEN
 IN BREAKDOWN OF PANELS AND LOAD
 CALCULATIONS.
 PLEASE ALSO SEE DE-RATING OF SUB PANELS
 MAY NOT BE DONE FOR ALL MOTOR/HEAT LOADS
 .
  
  
 PELASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  