| 2006-02-07 00:00:00 | ******* UNSAT ****** |
| | |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW WHICH NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: PLEASE SEE NOTE # 4 FROM |
| | PREVIOUS REVIEW. PLEASE INDICATE THE KW |
| | RATINGS FOR POOL HEATERS. |
| | PLEASE BE SURE ALL CONTINUOUS LOADS ARE |
| | FIGURED AT 125%, POOL PUMP(S), POOL |
| | HEATER(S). |
| | PLEASE SEE LOAD SHOWN ON POOL PANEL IS |
| | ALREADY SHOWN AT 96A'S WHICH IS OF |
| | CONCERN WITH THE ADDED LOADS FROM |
| | ORIGINAL PLANS. |
| | |
| | |
| | 2)NOTE: PLEASE INDICATE ALL THE KW |
| | RATINGS FOR A/C EITH CU'S OR AHU'S |
| | WHICHEVER LOAD IS GREATER. |
| | THE LOADS SHOWN ON THE PANEL SCHEDULE(S) |
| | MENTIONS THE LOADS ALREADY @65%, HOWEVER |
| | EACH AHU SEEMS TO BE ABOUT 5KW OR SO, |
| | WHICH @65% WOULD NOT BE THE LOADS SHOWN. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE ALL SUB PANELS ARE |
| | NOW INDICATED AS "GARAGE PANELS"? |
| | PLEASE CORRELATE THE IDENTIFICATION WITH |
| | RISER. |
| | |
| | 4)NOTE: PLEASE SEE RISER NOW SHOWS A |
| | DISCONNECTING MEANS AHEAD OF THE GARAGE |
| | PANEL "E', YET PLANS DO NOT SHOW THIS |
| | DISCONNECT. PLEASE ALSO SEE RISER WHICH |
| | SHOWS A MCB IN PANEL AT GARAGE? |
| | PLEASE CORRLELATE. |
| | PLEASE SEE THE EQUIPMENT GROUNDING |
| | CONDUCTOR FROM PANEL "C" IN MAIN HOUSE |
| | IS NOW MISSING TO THE GARAGE PANEL "E". |
| | PLEASE SEE 250.32. |
| | AN EQUIPMENT GROUNDING CONDUCTOR IS |
| | REQUIRED; THE ONLY EXCEPTION IS IF THERE |
| | ARE COMPLETELY NO OTHER METAL PARTS |
| | CONNECTED BETWEEN BLDGS. THIS WOULD BE , |
| | WATER PIPES, CATV, PHONE ETC. |
| | THE CHANCES OF THERE BEING NO METALS |
| | PATHS OR FUTURE PHONE ETCIS VERY |
| | UNLIKELY. |
| | PLEASE INCLUDE THE EQUIPMENT GROUND AS |
| | SHOWN ON PREVIOUS PLANS. |
| | |
| | 5)NOTE: PLEASE SEE LOAD CALCUALTIONS |
| | PROVIDE DO NOT PROVIDE ENOUGH |
| | INFORMATION FOR REVIEW OF MINS' |
| | REQUIRED. PLEASE EITHER SHOW A BREAK |
| | DOWN OR INDICATE THE VA/KW ON PANEL |
| | SCHEDULES. ( SMALL APPL, LAUNDRY/WASHER, |
| | DRYER ETC ETC. |
| | 220,215.5 |
| | |
| | NEW NOTE: |
| | |
| | 6)NOTE: PLEASE SEE GARAGE SHOWS A 220V |
| | RECEPT, HOWEVER THIS IS NOT ON PANEL |
| | SCHEDULE FOR GARAGE. |
| | 215.5 |
| | |
| | ** PLEASE KNOW, THIS OFFICE IS UNABLE TO |
| | VERIFY CORRECT OCP AND AWG FOR SOME |
| | CIRCUITS AS LOADS ARE NOT SHOWN OR GIVEN |
| | IN BREAKDOWN OF PANELS AND LOAD |
| | CALCULATIONS. |
| | PLEASE ALSO SEE DE-RATING OF SUB PANELS |
| | MAY NOT BE DONE FOR ALL MOTOR/HEAT LOADS |
| | . |
| | |
| | |
| | PELASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |