Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-26 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) THREE STORY R-3 TYPE V STRUCTURE IS
 REQUIRED TO BE FIRE SPRINKLED OR BE ONE
 HOUR FIRE PROTECTED. SEE FBC TABLES 500
 AND 600.
  
 5) SPECIFY LOCATIONS AND MATERIALS USED
 FOR DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLIES. SEE FBC 2305.2.2
  
 6) SPECIFY FIREBLOCKING AS REQUIRED IN
 CONCEALED SPACES. SEE FBC 705.3.1 AND
 2305.1.
  
 7) REVISE NOTES ON SHEET A1 UNDER
 SECURITY & FORCED ENTRY PREVATION THAT
 REFERENCE THE SFBC. THE CURRENT CODE IS
 THE FLORIDA BUILDING CODE.
  
 8) THE STRUCTURE IS LOCATED IN AN "A5"
 FLOOD ZONE AN ELEVATION CERTIFICATE WILL
 BE REQUIRED. INDICATE THE PROPOSED
 FINISHED FLOOR ELEVATION. THE MINIMUM
 ELEVATION IS 7.5 FEET.
  
 9) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOIL TEST REOPRT FROM SOILS
 ENGINEER. SOIL MUST HAVE A BEARING
 CAPACITY OF 3000 PSF PER PLANS.
  
 10)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 SAFETY GLASS IS REQUIRED WITHIN THREE
 FEET HORIZONTALLY OF A TUB OR SHOWER.
  
 11) PROVIDE AT LEAST ONE BATHROOM ON THE
 GROUND FLOOR WITH A DOOR THAT HAS A 29"
 CLEAR OPENING. SEE FBC 11-11. MUST BE
 FULL BATH, UNLESS ONLY A HALF BATH IS
 PROVIDE AT GRADE LEVEL.
  
 12) PROVIDE DETAILS OF STAIRS. SHOW
 COMPLIANCE WITH FBC 1007.3 EXCEPTION (1)
 WHICH REQUIRES THE SUM OF 2 RISERS AND A
 TREAD (EXCLUSIVE OF THE NOSING) TO BE
 NOT LESS THAN 24" NOR MORE THAN 25".
 SPECIFY HANDRAILS AS REQUIRED BY FBC
 1007.5 AND INDICATE HANDRAIL DIMENSIONS
 THAT COMPLY WITH 1007.5.3.
  
 13)1007.8.1 WINDERS SHALL HAVE A
 MINIMUM TREAD DEPTH OF 6" AT THE NARROW-
 EST EDGE & SHALL HAVE A MINIMUM TREAD
 DEPTH OF 11" AT A POINT 12" FROM THE
 NARROW EDGE. WINDERS SHALL BE PERMITTED
 TO BE USED AS A COMPONENT IN MEANS OF
 EGRESS WITHIN A DWELLING UNIT.
  
 14) FBC 2305.1.4 REQUIRES FIREBLOCKING
 AT CONCEALED SPACES BETWEEN STAIR
 STRINGERS AT THE TOP AND BOTTOM OF RUNS.
 INDICATE THE LOCATIONS AND MATERIALS TO
 BE USED.
  
 15) ON SHEET A2 THE STAIR INFORMATION
 GIVEN FOR THE GROUND FLOOR AND SECOND
 FLOOR APPEARS TO BE REVERSED. PLEASE
 CORRECT.
  
 16) PROVIDE STRUCTURAL DETAILS FOR THE
 ALUMINUM CANOPY OR APPLY UNDER SEPARATE
 PERMIT. INDICATE DIMENSIONS, ATTACHMENT
 DETAILS, FASTENERS, ENGINEERING,
 WINDLOADS, ETC.
  
 17)2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGHT OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGHT
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR. WINDOWS IN BEDROOM 1 DOES
 NOT COMPLY WITH NET CLEAR OPENING HEIGHT
  
 18) PROVIDE MANUFACTURER'S SPECS. AND
 LISTING INFORMATION FOR THE PRE-FAB FIRE
 PLACE.
  
 19) PROVIDE STRUCTURAL DETAILS AND
 ENGINEERING FOR THE GLASS AND ALUMINUM
 BALCONY GUARDRAILS. INDICATE ATTACHMENTS
 AT WALLS AND FLOOR, FASTENERS, ETC.
  
 20) GLASS USED FOR GUARDRAILS SHALL
 COMPLY WITH FBC 2405.5.
  
 21) GUTTERS AND LEADERS SHALL BE SIZED
 AND DISCHARGED IN ACCORDANCE WITH FBC
 PLUMBING CODE PER 1503.4.3.
  
 22) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 23) SPECIFY TERMITE PROTECTION PER FBC
 1816.1.
  
 24) FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
 SPECIFY ON PLANS.
  
 25) 1707.4.4.2 WHERE BUCK THICKNESS IS
 LESS THAN 1-1/2" WINDOW AND DOOR SHALL
 BE ANCHORED THROUGH THE BUCK DIRECTLY TO
 THE SUBSTRATE. REVISE BUCK DETAILS.
  
 26) PROVIDE HURRICANE ANCHOR SCHEDULE &
 INDICATE THE LOADS TO BE RESISTED.
  
 27) INDICATE CONNECTIONS FOR WOOD
 GIRDERS AT WALLS, COLUMNS, ETC.
  
 28) PROVIDE STRUCTURAL DETAIL FOR
 PARAPET WALLS.
  
 29) PROVIDE STRUCTURAL DETAILS FOR THE
 CONCRETE BALCONIES. INDICATE SIZES,
 SPACING OF STEEL REINFORCEMENT, ETC.
  
 30) THE FOOTING AND COLUMN SCHEDULES DO
 NOT CORRESPOND WITH THE I.D. TAGS GIVEN
 ON THE PLANS.
  
 31) PROVIDE DETAILS OF THE STEEL COLUMNS
 INDICATE ATTACHMENTS AT TOP AND BOTTOM
 OF COLUMNS, FASTNERS ETC.
  
 32) SPECIFY THE TIE BEAMS SIZE, STEEL
 REINFORCEMENT, ETC. AT EACH FLOOR.
  
 34) PROVIDE A DETAIL INDICATING THE
 FRAMING THAT WILL BE USED TO SUPPORT THE
 FLOOR AND CARRY THE CEILING AT THE WALLS
 THAT PARALLEL THE FLOOR/CEILING JOISTS.
  
 35) SPECIFY THE EMBEDDMENT DEPTH OF THE
 WEDGE ANCHORS AT THE 2X8 LEDGER AT THE
 WALL SECTION ON A5.
  
 36) REVISE GENERAL NOTE A ON 5.3 TO
 REFERENCE THE FBC.
  
 37) SHEET A3 SHOWS A WOOD DECK OVER A
 CONCRETE SLAB AND S2 SHOWS WOOD TRUSSES
 IN THE SAME AREA. PLEASE CLARIFY.
 INDICATE HOW THIS AREA WILL BE MADE
 WATER TIGHT, HOW DECK WILL BE FASTENED
 TO CONCRETE, ETC.
  
 38) THE SQUARE FEET OF CONDITION AREA
 IS DIFFERENT FROM THE A/C AREA LISTED ON
 THE PLANS. PLEASE CLARIFY.
  
 39) SPECIFY THE AMOUNT OF ROOF SLOPE ON
 THE PLANS. SEE FBC 1508.3.1 FOR REQUIRED
 MINIMUM FOR BUILT UP ROOFING.
  
 40)REVIEW THE EAST WALL OF THE STRUCTURE
 FOR SHEAR WALL REQUIREMENTS AND PROVIDE
 CALCULATIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202