| Plan Review Notes For Permit 02101307 |
| Permit Number |
02101307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE CORRELATE AHU`S ON MECH | | | PLANS W/ UNITS SHOWN ON ELECTRICAL | | | PLANS. PLEASE NOTE CIRCUITING NEED TO | | | CORRELATE WITH SUBMITTED PANEL SCHEDULES | | | PLEASE NOTE FOUR AHU`S ARE SHOWN ON | | | PLANS AND ONLY THREE CU`S ? | | | PLEASE CLARIFY | | | | | | 2)NOTE: PLEASE NOTE DISCONNECT FOR | | | ELEVATOR EQUIPMENT MUST BE SERVICE | | | ENTRANCE RATED AND SUBMIT AIC RATING FOR | | | DISC. 215-5,110-9 | | | | | | 3)NOTE: PLEASE CLARIFY SIZE OF COLD | | | WATER PIPE ON RISER DIAGRAM 3/9"? | | | | | | 4)NOTE: PLEASE SHOW ROOM DESIGNATION ON | | | PLANS. | | | | | | 5)NOTE: PLEASE NOTE CLEARENCE FOR CU | | | DISC`S PER 110-26 | | | | | | 6)NOTE: PLEASE NOTE PANELS ARE SHOWN | | | W/OUT MCB`S? 225-31/240/ RISER SHOWS | | | 2P/200`S | | | 7)NOTE: PLEASE NOTE LOAD CALCULATIONS | | | DO NOT INCLUDE SAUNA EQUIPMENT/LOADS? | | | PLEASE CORRELATE. | | | | | | 8)NOTE: PLEASE NOTE , PANEL SCHEDULE | | | ONLY SHOWS ONE WATER HEATER? PLEASE | | | CLARFIY, SECOND WATER HEATER AT 1500W? | | | | | | 9)NOTE:PLEASECLARIFY LOADS SHOWN FOR | | | A/C CU`S. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|