Plan Review Notes
Plan Review Notes For Permit 02101307
Permit Number 02101307
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-05 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CORRELATE AHU`S ON MECH
 PLANS W/ UNITS SHOWN ON ELECTRICAL
 PLANS. PLEASE NOTE CIRCUITING NEED TO
 CORRELATE WITH SUBMITTED PANEL SCHEDULES
 PLEASE NOTE FOUR AHU`S ARE SHOWN ON
 PLANS AND ONLY THREE CU`S ?
 PLEASE CLARIFY
  
 2)NOTE: PLEASE NOTE DISCONNECT FOR
 ELEVATOR EQUIPMENT MUST BE SERVICE
 ENTRANCE RATED AND SUBMIT AIC RATING FOR
 DISC. 215-5,110-9
  
 3)NOTE: PLEASE CLARIFY SIZE OF COLD
 WATER PIPE ON RISER DIAGRAM 3/9"?
  
 4)NOTE: PLEASE SHOW ROOM DESIGNATION ON
 PLANS.
  
 5)NOTE: PLEASE NOTE CLEARENCE FOR CU
 DISC`S PER 110-26
  
 6)NOTE: PLEASE NOTE PANELS ARE SHOWN
 W/OUT MCB`S? 225-31/240/ RISER SHOWS
 2P/200`S
 7)NOTE: PLEASE NOTE LOAD CALCULATIONS
 DO NOT INCLUDE SAUNA EQUIPMENT/LOADS?
 PLEASE CORRELATE.
  
 8)NOTE: PLEASE NOTE , PANEL SCHEDULE
 ONLY SHOWS ONE WATER HEATER? PLEASE
 CLARFIY, SECOND WATER HEATER AT 1500W?
  
 9)NOTE:PLEASECLARIFY LOADS SHOWN FOR
 A/C CU`S.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372