Plan Review Notes
Plan Review Notes For Permit 02101276
Permit Number 02101276
Review Stop M
Sequence Number 1
Notes
Date Text
2002-11-01 00:00:00DENIED:MECHANICAL PERMIT 02101278
  
 1.PROVIDE DUCT LAYOUT SIZE, MATERIAL,
 AND CFM DISTRIBUTION.
  
 2.AS PER 2001 FBC(M) 601.4, WHERE
 RETURNS ARE CENTRALLY LOCATED,
 PRESSURE DIFFERENTIALS SHALL BE
 LIMITED TO .001 IN WC. PROVIDE
 RETURN AIR DUCTS OR AIR TRANSFER
 FROM BEDROOM AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.