| Plan Review Notes For Permit 02101188 |
| Permit Number |
02101188 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-24 00:00:00 | PROVISO: | | | | | | EXHAUST FANS SHALL TERMINATE: | | | | | | 1.A MINIMUM OF 10FT FROM ANY ADJACENT | | | BUILDINGS, PROPERTY LINE, AND AIR | | | INTAKES. | | | | | | 2.EXHAUST FLOW DIRECTED UP & AWAY FROM | | | THE SURFACE OF THE ROOF & A MINIMUM | | | OF 40" ABOVE THE ROOF SURFACE. | | | NFPA 96 4-8.2 (A) & (B). | | | | | | AS PER 2001 FBC(M) 506.3.9, GREASE DUCT | | | SHALL HAVE 1/4" PER FT SLOPE FOR DUCTS | | | LESS THAN 75 FT, 1" PER FT GREATER THAN | | | 75 FT. | | | | | | PLEASE NOTE ALL WELDS TO BE INSPECTED | | | PRIOR TO COVERING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|