Plan Review Notes
Plan Review Notes For Permit 02101141
Permit Number 02101141
Review Stop R
Sequence Number 2
Notes
Date Text
2003-01-07 00:00:00BUILDING DENIED
  
 1) INDICATE THE NEGATIVE AND POSITIVE
 DESIGN WINDLOAD PRESSURES FOR ALL
 EXTERIOR OPENINGS.
  
 2) REVISE THE TYPICAL WALL SECTION ON A5
 TO INDICATE THE FINISH FLOOR ELEVATION
 TO BE A MINIMUM OF 4" ABOVE FINAL GRADE
 AS REQUIRED BY CITY OF WPB AMENDMENTS TO
 FBC 1804.1.7. THE 6" MINIMUM INDICATED
 WILL NOT PROVIDE THE MINIMUM 12" BELOW
 GRADE REQUIRED TO THE BOTTOM OF THE
 FOOTINGS WITH 16" DEEP FOOTINGS.
  
 3) THE REAR ELEVATION ON A-4 AND SECTION
 A-A ON A-5 STILL SHOW THE BUTT GLASS
 WINDOW, WHICH WAS CHANGED ON THE FLOOR
 PLAN.
  
 4) SPECIFY THE MINIMUM REQUIRED EMBED
 DEPTH FOR THE 1/2" ANCHOR BOLTS USED TO
 ATTACH THE GARAGE DOOR BUCKS IN THE
 DETAIL ON A5.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - OUTSWING DOUBLE DOOR WITHOUT SIDELITES
 - SINGLE HUNG WINDOWS
 - SINGLE OUTSWING FRENCH DOORS
 - FIXED GLASS WINDOWS (ARCHED, OVAL,
 SQUARE, ETC.)
 - SLIDING GLASS DOORS
 - STRUCTURAL MULLIONS
 - HORIZONTAL SLIDING WINDOWS
 NOTE: PRODUCT APPROVALS MUST MATCH THOSE
 SHOWN ON PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202