Plan Review Notes
Plan Review Notes For Permit 02101141
Permit Number 02101141
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-21 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PLEASE REVISE PLAN NOTE #11 ON C1,
 HURRICANE SHUTTERS ARE REQUIRED IN THE
 CITY OF WPB AND IT IS NOT IN A HVHZ.
  
 4) PLEASE REVISE FRAMING NOTE #15 ON C1,
 ASTM C 1063 REQUIRES 3/8" RIB METAL LATH
 TO BE FASTENED AT EACH RIB (4").
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE INTERNAL PRESSURE
 COEFFICIENT ON THE PLANS (+ OR - .18 FOR
 ENCLOSED STRUCTURES).
  
 6) THE LINES INDICATING THE FOOTINGS FOR
 THE THREE COLUMNS AT THE COVERED PATIO
 ARE NOT SHOWN ON A2.
  
 7) THE F8 FOOTING AT THE COVERED ENTRY
 APPEARS TO HAVE DIFFERENT DIMENSIONS
 THAN THE ONES LISTED IN THE FOOTING
 SCHEDULE. PLEASE CLARIFY.
  
 8) THE DIMENSIONS IN THE FOOTING
 SCHEDULE FOR THE F3 FOOTING FOR THE
 STEEL COLUMN AT THE FOYER DO NOT APPEAR
 TO BE CORRECT. PLEASE CLARIFY.
  
 9) SPECIFY ACCESS TO ATTIC SPACE AS
 REQUIRED BY FBC SECTION 2309.6.
  
 10) PROVIDE ENGINEERING FOR BUTT GLASS
 AS REQUIRED BY FBC 2406.2.
  
 11) PROVIDE A FULL BATH ROOM WITH A DOOR
 THAT HAS A 29" CLEAR OPENING AS REQUIRED
 BY FBC 11-4.23.2.
  
 12) INDICATE THE POSITIVE AND NEGATIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 OPENINGS.
  
 13) REVISE THE TYPICAL WALL SECTION ON
 A5 TO INDICATE THE FINISH FLOOR
 ELEVATION TO BE A MINIMUM OF 4" ABOVE
 FINAL GRADE AS REQUIRED BY CITY OF WPB
 AMENDMENTS TO FBC 1804.1.7. THE 6" MIN.
 LISTED WILL NOT PROVIDE THE MIN. 12"
 BELOW GRADE TO BOTTOM OF FOOTING WITH
 16" DEEP FOOTINGS.
  
 14) SPECIFY THE MINIMUM REQUIRED EMBED
 DEPTH FOR THE 1/2" ANCHOR BOLTS USED TO
 FASTEN THE GARAGE DOOR BUCKS ON A5.
  
 15) PLEASE REVIEW THE BOND BEAM OVER THE
 THE OPENING FOR THE BUTT GLASS. THE
 (BB1) 8X8 WITH ONE #5 DOES NOT APPEAR TO
 BE ADEQUATE. PLEASE PROVIDE COMPLETE
 ENGINEERED STRUCTURAL ANALYSIS OF THIS
 BEAM.
  
 16) CONNECTION DETAIL 16 ON A6 AT HIS
 W.I.CLOSET IS INDICATED AT THE WRONG
 LOCATION. IT IS NOT INDICATED AT THE
 GIRDER TRUSS. ALSO, REVIEW LOCATION OF
 VERTICAL REINFORCEMENT AT THIS LOCATION.
  
 17) NO DETAIL IS GIVEN FOR TAG 17 ON A6.
  
 18) THE WRONG CONNECTION DETAIL IS GIVEN
 FOR THE GIRDER AT THE COVERED ENTRY.
 10 ON A6 IS NOT CORRECT.
  
 19) THE TAG FOR DETAIL 1 ON A6 IS SHOWN
 AT THE WRONG LOCATION ON THE COVERED
 PORCH.
  
 20) NO TAG AND DETAIL IS INDICATED FOR
 THE CONNECTOR AT THE EXTERIOR WALL
 BETWEEN DINING ROOM AND KITCHEN FOR THE
 GIRDER. NOTE ON A7 REFERS TO DETAIL ON
 A6.
  
 21) INDICATE ON THE PLANS THE ROOF
 SHEATHING NAILING REQUIREMENTS AND ROOF
 ZONES AS REQUIRED BY CITY OF WPB
 AMENDMENTS TO FBC TABLE 2306.1.
  
 22) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - OUTSWING DOUBLE DOOR WITHOUT SIDELITES
 - OVERHEAD GARAGE DOORS (INFORMATION
 SUBMITTED IS NOT ACCEPTABLE)
 - OUTSWING SINGLE FRENCH DOOR
 - HORIZONTAL SLIDING WINDOW
  
 23) IF NORANDEX PRODUCTS DO NOT HAVE
 SBCCI OR METRO-DADE PRODUCT APPROVALS,
 SITE SPECIFIC ENGINEERING IS REQUIRED.
 THE SITE SPECIFIC PRODUCT SUBMITTAL
 FORMS MUST HAVE THE WET SIGNATURE,
 EMBOSSED SEAL AND DATE OF THE ENGINEER
 CERTIFYING THE PRODUCT AND THE SAME IS
 REQUIRED FOR THE DESIGNER OF RECORD WHO
 IS CERTIFYING THAT THE PRODUCT IS
 APPROVED FOR INSTALLATION IN THE
 STRUCTURE. THE LOCATION OR SITE OF THE
 JOB IS REQUIRED TO BE ON THE FORM. THE
 SPECIFIC PRODUCTS THAT ARE BEING USED
 MUST BE LISTED ON THE FORMS AND SHOWN IN
 THE DRAWINGS OR AN ENGINEERED ANALYSIS
 FOR A DIFFERENT SIZE OR SHAPE BASED ON
 THE TESTED PRODUCT WILL BE REQUIRED.
  
 24) THE ENERGY CALCULATION FORMS ARE
 REQUIRED TO BE SIGNED BY THE OWNER/AGENT
  
 25) THE CONDITIONED FLOOR AREA LISTED ON
 THE ENERGY CALCULATIONS DOES NOT MATCH
 THE A/C FLOOR AREA GIVEN ON THE PLANS.
 PLEASE CORRECT.
  
 26) THE FLOOD ZONE INFORMATION LISTED ON
 THE SURVEY IS NOT CORRECT. STRUCTURE IS
 IN A "B" FLOOD ZONE. PLEASE CORRECT.
  
 27) PROVIDE AN INSTALLATION SCHEDULE AND
 A KEY PLAN FOR THE HURRICANE PANELS.
  
 PLEASE INSERT NEW SHEETS INTO PLANS AND
 REMOVE VOIDED ONES. RETURN VOIDED SHEETS
 ALONG WITH RESUB. THIS WILL HELP TO
 EXPEDITE THE PLAN REVIEW PROCESS.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved