| Plan Review Notes For Permit 02101141 |
| Permit Number |
02101141 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT. MAINS/PANELS | | | BRKRS TO BE RATED FOR AVAILABLE FAULT | | | CURRENT. 110-9 | | | | | | 2)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) PER 210-52D,210-11-C-3 | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROETCTED CIRCUITS PER 210-12. | | | | | | 4)NOTE: PLEASE SEE OUTLET SPACING FOR | | | KITCHEN COUNTERSPACE PER 210-52-C-1 | | | | | | 5)NOTE: PLEASE NOTE SIZING OF OCP FOR | | | AHU`S TO MEET 424-3B | | | | | | 6)NOTE: PLEASE CLARIFY HOW THREEE AHU | | | LOADS AT 9.6 KW AT 65% IS 13KW? | | | | | | PLEASE COMPLETE PLANS AND SUBMIT FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | EELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|