| Permit Number |
02101140 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING | | | FOR ALL NEW SERVICE EQUIPMENT. MAINS, | | | PANELS, BRKRS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT.110-9/215-5 | | | | | | 2)NOTE: PLEASE LIST THE REQ`D BATH | | | CIRCUIT(S) PER 210-52D,210-11-C-3 | | | | | | 3)NOTE: PLEASE LIST THE REQ` ARC FAULT | | | PROTECTED CIRCUITSPER 210-12 | | | | | | 4)NOTE: PLEASE NOTE SIZING FOR OCP FOR | | | AHU`S TO BE SIZED PER 424-3B | | | | | | 5)NOTE: PLEASE CLARIFY HOW THREE AHU | | | LOADS AT 9.6KW AND ARE AT 65% = TO 13KW | | | | | | | | | PLEASE COMPLETEAND SUBMITFOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|