| 2003-03-28 00:00:00 | THE EXIT STAIRS FROM THE MEZZANINE ARE | | | REQUIRED TO BE ENCLOSED IN FIRE RATED | | | CONSTRUCTION IN ACCORDANCE WITH FBC | | | 1005.7.3.THE TRAVEL DISTANCE EXCEEDS | | | 75'. | | | | | | PORTAFAB PLANS SHEET 1 OF 3.WHAT ARE | | | THE "SUPPORT BOARDS" | | | | | | WHAT ARE THE COLUMNS THAT SUPPORTS THE | | | W10X39?INCLUDE THE CONNECTION AT THE | | | BOTTOM. | | | | | | WHAT DO THE W10X15 BEAMS REST ON AT THE | | | WALL ENDS?COLUMNS? THE VINYL AND | | | PAPERWALL PANELS? | | | | | | WHAT IS THE DECKING SHOWN AS "DUST | | | COVER"HOW IS IT FASTENED THE W10 | | | BEAMS? | | | | | | WHAT IS THE RISE AND RUN OF THE | | | "U-SHAPED BOCA STAIR"?HANDRAIL | | | DETAILS?LANDING CONSTRUCTION AND | | | SUPPORT?DESIGN LOAD? | | | | | | ALSO, PLEASE PROVIDE A COPY OF THE | | | STRUCTURAL CALCULATIONS DEMOSTRATING | | | THE MEZZANINE CAN SUPPORT THE MINIMUM | | | 125 PSF LIVE LOAD. | | | | | | AS PREVIOUSLY NOTED IMPACT FEES MUST BE | | | PAID TO THE COUNTY BEFORE A PERMIT MAY | | | BE ISSUED. |
|