| 2003-02-06 00:00:00 | ************** UNSAT *************** |
| | |
| | PLEASE NOTE, SOME NOTES FROM |
| | FIRST REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE OCP FOR AHU`S 1&2, |
| | SHOWS 40A OCP FOR 10KW HEAT(MECH PLANS) |
| | PLEASE ADJUST AQND CORRELATE MECH AND |
| | ELECTRICAL PLANS. PLEASE ALSO SIZE OF |
| | OCP PER 424-3 IF AHU'S ARE INDEED 10KW |
| | AS SHOWN ON M SHEETS. PLEASE SEE LOADS |
| | SHOWN ON PANEL SCHEDULE, LOAD SHOWN |
| | EXCEEDS LOADS SHOWN ON LOAD CALCULATIONS |
| | FOR CHILLER/COND UNITS. THE HIGHER OF |
| | THE TWO LOADS NEED TO BE SHOWN IN LOAD |
| | CALCS. PLEASE RE-DO LOAD CALCULATIONS |
| | TO REFLECT LOADS OF AHU`S . SHOWN AT |
| | 4.3 PER PHASE (CHILLERS AT 3.3 PER PHASE |
| | )?? |
| | |
| | 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. 215-3,230-42 ETC. |
| | |
| | 3)NOTE: PLEASE PLACE NOTE ON E-2, |
| | "NO HAZARDOUS MATERIALS TO BE USED AND |
| | DOES NOT MEET ANY LOCATIONS IN ART 500 |
| | IN THE NEC". |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |
| | |
| | |
| | PLEASE SEE FIRE REVIEW COMMENTS THAT |
| | WILL AFFECT ELECTRICAL PLANS. |