| Date |
Text |
| 2002-12-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBVC-2001 BUILDING |
| | |
| | 1) SHT A2 PLEASE PROVIDE CALCULATIONS |
| | FOR MINIMUM FACILITIES PER TABLE 1003.1 |
| | FBC-BLDG AND 403.1 FBC-PLMG. |
| | 2) SHT A2 IF TOILET ROOMS ARE PROVIDED, |
| | THEN EACH PUBLIC AND COMMON USE TOILET |
| | ROOM SHALL COMPLY WITH 11-4.22. SEC. |
| | 11-4.1.3(11) |
| | 3) SHT A2 MENS REST ROOM, IF TOILET |
| | STALLS ARE PROVIDED, THEN AT LEAST ONE |
| | SHALL BE A STANDARD STALL COMPLYING WITH |
| | 11-4.17 PER 11-4.22.4. SEE 11-4.17.3 FOR |
| | SIZE AND ARRANGEMENT. LAV REQUIRED IN |
| | STALL. |
| | 4) SHT A2 SHOWER ROOM, SHOWER SHALL COM- |
| | PLY WITH 11-4.21 AND ALL SUBSECTIONS. |
| | SHOW DETAIL. |
| | 5) SHT A2 EMPLOYEE'S LOUNGE, SINK SHALL |
| | COMPLY WITH 11-4.24 AND ALL SUBSECTIONS. |
| | PLEASE SHOW DETAILS. |
| | 6) SHT A2 DRINKING FOUNTAIN, SHOW DETAIL |
| | FOR COMPLIANCE WITH SEC. 11-4.15 AND ALL |
| | SUBSECTIONS. ALSO SEC. 11-4-1-3(10)(A) |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 7) SHT A2 MENS REST ROOM, URNAL SHALL |
| | COMPLY WITH 11-4.18 AND ALL SUBSECTIONS. |
| | SHOW DETAIL. |
| | 8) SHT A5 DETAIL #5 PER FBC SEC 1503.4.2 |
| | OVERFLOW SCUPPERS SHALL BE A MINIMUM OF |
| | 4 INCHES IN HEIGHT AND SHALL BE PLACED |
| | IN WALLS OR PARAPETS WITH THE INLET FLOW |
| | LINE NOT LESS THAN 2 INCHES ABOVE THE |
| | ROOF SURFACE, EXCLUDING SUMPS, OR MORE |
| | THAN 4 INCHES ABOVE THE ROOF SURFACE. |
| | PLANS SHOW 5" TO INLET FLOW LINE. |
| | 9) SHT P-1 P/T LINE FROM WATER HEATER |
| | SHALL NOT BE TRAPPED. SEC 504.7.1 |
| | 10) SHT P-1 WATER ISOMETRIC, WATER HAM- |
| | MER ARRESTORS REQUIRED IN SEC 604.9 |
| | SHALL BE LOCATED NEAR FIXTURES IN AN |
| | "EFFECTIVE RANGE" NOT AT TOP OF DROP AS |
| | SHOWN. PER PDI-WH 201 AND MANUF. INSTALL |
| | ATION INSTRUCTIONS. |
| | 11) BACKFLOW REQUIRED ON WATER SERVICE. |
| | 12) SHT P-1 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL REQUIRED PER SEC 607.3 |
| | AND 607.3.2 PLEASE ADD TO DETAIL |
| | 13) SHT P-2 PLEASE SHOW LOCATION ON |
| | SCUPPER DRAINS. SHOW SIZE OF EACH |
| | SCUPPER DRAIN AND SQUARE FOOTAGE BEING |
| | DRAINED THRU EACH SCUPPER. |
| | 14) SHT P-3 MATERIALS & EQUIPMENT (L) & |
| | EXECUTION OF WORK (F) AIR CHAMBERS ARE |
| | NOT APPROVED. PLEASE DELETE REFERENCES. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |