Plan Review Notes For Permit 02101073
Permit Number 02101073
Review Stop M
Sequence Number 1
Notes
Date Text
2002-10-30 00:00:00DENIED:
  
 PROVIDE DETAIL AS THE MOUNTING OF THE
 CONDENSER UNIT INSTALLED ON THE ROOF.
 SHOW COMPLIANCE WITH 2001 FBC 1511.7.
  
 PLEASE NOTE, SUFFICIENT CLEARENCE
 REQUIRED FOR SERVICE & REPLACEMENT AS
 PER 2001 FBC(M) 306.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.