| Plan Review Notes For Permit 02101068 |
| Permit Number |
02101068 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-12 00:00:00 | DENIED:MECHANICAL PERMIT 02101090 | | | | | | PLAN SHEET A-1 INDICATES THE MECH/ELEC | | | ROOM HAS A 1 HR RATING.NO FIRE DAMPERS | | | ARE INDICATED ON PLAN. | | | | | | PLEASE NOTE, AS PER 2001 FBC(M) 401.5, | | | OUTSIDE AIR EXHAUST SHALL BE LOCATED A | | | MINIMUM OF 10 FT FROM LOT LINES OR | | | BUILDINGS ON THE SAME LOT.401.5.2, | | | EXHAUST AIR SHALL NOT BE DIRECTED ONTO | | | WALKWAYS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|