Plan Review Notes
Plan Review Notes For Permit 02101068
Permit Number 02101068
Review Stop M
Sequence Number 1
Notes
Date Text
2002-11-12 00:00:00DENIED:MECHANICAL PERMIT 02101090
  
 PLAN SHEET A-1 INDICATES THE MECH/ELEC
 ROOM HAS A 1 HR RATING.NO FIRE DAMPERS
 ARE INDICATED ON PLAN.
  
 PLEASE NOTE, AS PER 2001 FBC(M) 401.5,
 OUTSIDE AIR EXHAUST SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT.401.5.2,
 EXHAUST AIR SHALL NOT BE DIRECTED ONTO
 WALKWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.