Plan Review Notes
Plan Review Notes For Permit 02100867
Permit Number 02100867
Review Stop B
Sequence Number 2
Notes
Date Text
2002-11-27 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02100867
 ADDRESS: 3042 SANTA MARGARITA RD
 CONT: DOUBLE R BLDG CORP
 TELL # (954)796-0777
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO******
  
 1) SOILS REPORT IS TO BE PART OF PLAN
 REVIEW TO DETERMINE THE MINIMUM SAFE
 BEARING VALUE, CONTRACTOR IS WORKING AT
 HIS OWN RISK WITHOUT SOILS REPORT TO
 THIS OFFICE. ADDITIONAL FILL SHALL ALSO
 REQUIRE DENSITY TESTING BEFORE THE
 PLACEMENT OF CONCRETE.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SOLID CORE PAIR OF FRONT DOORS
 B) FRENCH DOORW/ GLAZING
 C) GLASS BLOCK- THIN, THICH OR SOLID
 WALL FOR WIND/LARGE MISSLE IMPACT
 THESE REPORTS ARE REQUIRED TO THIS
 OFFICE BEFORE BUCK INSPECTION(119).
  
 3) GLASS BLOCK ON ZERO LOT LINE SIDE
 REQUIRES 1 HR RATING, PRODUCT TESTING
 REPORT FOR FIRE RATING TO THIS OFFICE
 BEFORE BUCK INSPECTION(119).
  
 4) ROOF SHEATHING A-9 ZONE 3 RED LINED
 MEAN ROOF HEIGHT > 25', ZONE 3 REQUIRES
 RING SHANK NAILS
 BUILDING PLAN REVIEW
 JIM WITMER