| Plan Review Notes For Permit 02100865 |
| Permit Number |
02100865 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-02-12 00:00:00 | ****** ************* UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE ITEMS REDLINED FROM | | | TWO PREVIOUS REVIEWS THAT HAVE NOT BEEN | | | CORRECTED. | | | NO SD IN KITCHEN, NFPA-72 8-1.4.2 | | | MISSING EQUIPMENT GRND FROM MAIN DISC | | | TO PANEL. SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|