Plan Review Notes
Plan Review Notes For Permit 02100865
Permit Number 02100865
Review Stop R
Sequence Number 1
Notes
Date Text
2002-11-20 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SIGNED AND SEALED COPY OF SOILS
 REPORT FROM SOILS ENGINEER.
  
 4) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 5) GLASS BLOCK ON THE ZERO LOT LINE IS
 REQUIRED TO HAVE A ONE HOUR FIRE
 RESISTANCE. PROVIDE MANUFACTURES
 SPECIFICATIONS AND LISTING INFORMATION
 FOR A ONE HOUR FIRE RATED GLASS BLOCK
 ASSEMBLY. REVISE GLASS BLOCK DETAIL ON
 A5 TO COMPLY WITH ONE HOUR FIRE RATED
 INSTALLATION.
  
 6) THE EXTERIOR WALL AT ZERO LOT LINE IS
 REQUIRED TO HAVE A CALCULATED FIRE
 RESISTANCE OF ONE HOUR ASSUMING EITHER
 SIDE OF THE WALL TO BE EXPOSED TO FIRE.
 THE SECOND FLOOR WOOD FRAME WALL DOES
 NOT COMPLY.
  
 7)ON C1,#11 OF PLAN NOTES SAYS HURRICANE
 SHUTTERS ARE REQUIRED IN HVHZ. CITY OF
 WPB IS NOT IN HVHZ, HOWEVER, IMPACT
 PROTECTION IS REQUIRED. PLEASE REVISE.
  
 8) ON C1, FRAMING NOTE #15 SPECIFIES
 FASTENER SPACING OF 6" O.C., ASTM C 1063
 REQUIRES 3/8" RIB METAL LATH TO BE
 FASTENED AT EACH RIB (4").
  
 9) INDICATE THE LOCATION AND MATERIALS
 USED TO PROVIDE DRAFTSTOPPING AT AREAS
 GREATER THAN 500 SQFT IN FLOOR/CEILING
 ASSEMBLIES. FBC 2305.2.2
  
 10) THE CITY OF WPB AMENDMENTS TO FBC
 SECTION 2111.1.9 REQUIRES A 1.5 INCH
 RECESS (WATER STOP) WHERE EXTERIOR WALL
 CMU BEAR ON A CONCRETE FLOOR SURFACE.
 PLEASE REVISE DETAILS ON A1 & A6.
  
 11) THERE IS NO F12 FOOTING INDICATED IN
 THE FOOTING SCHEDULE ON A1.
  
 12) THE MEASUREMENT DESIGNATIONS (FEET
 & INCHES) ARE NOT INDICATED FOR SOME OF
 THE DIMENSIONS LISTED IN THE FOOTING
 SCHEDULE ON A1.
  
 13) CITY AMENDMENTS TO THE FBC TABLE
 2306.1 REQUIRE RING SHANK NAILS IN ZONE
 3 WHEN THE MEAN ROOF HEIGHT IS 25' OR
 MORE. PLEASE REVISE.
  
 14) FBC 2309.6 REQUIRES ACCESS TO ATTIC
 SPACE, WHEN THE CLEAR ATTIC SPACE AT THE
 PEAK IS 24 INCHES. INDICATE ATTIC ACCESS
 OPENINGS TO ANY OF THE LOWER ROOF ATTICS
 THAT MEET THIS CRITERIA.
  
 15) PROVIDE DETAILS OF ATTACHMENT OF
 BALCONY RAILS INDICATING THAT THEY ARE
 ADEQUATE IN STRENGTH, DURABILITY AND
 ATTACHMENT AS REQUIRED BY FBC 1608.2.
  
 16) INDICATE FIREBLOCKING MATERIAL AND
 LOCATIONS AT STAIRS AS REQUIRED BY FBC
 SECTION 2305.1.4.
  
 17) DETAIL 8 ON A7 IS INDICATED ON THE
 FRAMING PLAN AT THE WRONG LOCATIONS IN
 TWO INSTANCES. PLEASE CORRECT.
  
 18) DETAIL 8 ON A7 INDICATES 3-1/4"
 HILTI-PINS WITH 4" EMBED. PLEASE
 CLARIFY.
  
 19) DETAIL 9 ON A7 IS SHOWN ON THE PLAN
 AT THE WRONG LOCATION. PLEASE CORRECT.
  
 20) DETAIL 13 ON A7 IS NOT INDICATED ON
 THE FRAMING PLAN.
  
 21) DETAIL 11A ON A7 IS INDICATED ON THE
 FRAMING PLAN AND THERE IS NO DETAIL
 GIVEN.
  
 22) DETAIL 12 ON A8 IS INDICATED ON THE
 FRAMING PLAN ON A7, BUT THERE IS NO
 DETAIL 12 GIVEN ON SHEET A8.
  
 23) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - HORIZONTAL STRUCTURAL MULLIONS
 (ONES SUBMITTED ARE FOR VERTICAL
 APPLICATIONS ONLY)
 - ROOFING MATERIALS
 - OVERHEAD GARAGE DOORS
 - FRENCH DOORS (WITH GLAZING IN DOORS)
  
 24) PROVIDE THE TEST REPORTS FOR IMPACT
 RESISTIBILITY FOR THE EXTERIOR DOORS AS
 REQUIRED BY GENERAL NOTES ON THE SITE
 SPECIFIC PRODUCT SUBMITTAL FORMS.
  
 25) THE SITE SPECIFIC PRODUCT APPROVAL
 SUBMITTAL FORMS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE DESIGNER OF
 RECORD OF THE STRUCTURE.
  
 PLEASE INSERT NEW SHEETS INTO PLANS AND
 REMOVE OLD ONES. PLEASE RETURN OLD
 SHEETS WITH RESUBMITTAL IN ORDER TO
 EXPEDITE PLAN REVIEW.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202