| Plan Review Notes For Permit 02100837 |
| Permit Number |
02100837 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-17 00:00:00 | PROVISO: | | | | | | 1.LOCATION OF THE AHU IN BEDROOM 3 - | | | ACCESS FOR THE AHU SHALL BE NO LESS | | | THAN 30" X 22" (2001 FBC(M) 306.3) | | | AS PER 2001 FBC CHAPTER 13 SECTION | | | 610.1.ABC.3.5.2, THE SERVICE PANEL | | | OF THE EQUIPMENT SHALL BE LOCATED | | | WITHIN 6 FT OF THE ATTIC ACCESS. | | | | | | 2.RETURN AIR REQUIRED FROM THE BEDROOM | | | AREAS2001 FBC(M) 601.4. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|