Plan Review Notes
Plan Review Notes For Permit 02100837
Permit Number 02100837
Review Stop M
Sequence Number 1
Notes
Date Text
2002-10-17 00:00:00PROVISO:
  
 1.LOCATION OF THE AHU IN BEDROOM 3 -
 ACCESS FOR THE AHU SHALL BE NO LESS
 THAN 30" X 22" (2001 FBC(M) 306.3)
 AS PER 2001 FBC CHAPTER 13 SECTION
 610.1.ABC.3.5.2, THE SERVICE PANEL
 OF THE EQUIPMENT SHALL BE LOCATED
 WITHIN 6 FT OF THE ATTIC ACCESS.
  
 2.RETURN AIR REQUIRED FROM THE BEDROOM
 AREAS2001 FBC(M) 601.4.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved