Plan Review Notes
Plan Review Notes For Permit 02100795
Permit Number 02100795
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-17 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE INDICATE COMPLETE G.E.C.
 SYSTEM PER 250-50.
  
 3} THE PLAN SHOWS #3 FEEDERS WITH A #8
 GROUND BETWEEN PANELS "A" & "B".TABLE
 #5 CALCULATION FOR THOSE CONDUCTORS IS
 .3285 AREA SQ. IN. PLEASE INDICATE
 CONDUIT TYPE BEING USED FOR FILL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL;
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392