| Plan Review Notes For Permit 02100795 |
| Permit Number |
02100795 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-17 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE INDICATE COMPLETE G.E.C. | | | SYSTEM PER 250-50. | | | | | | 3} THE PLAN SHOWS #3 FEEDERS WITH A #8 | | | GROUND BETWEEN PANELS "A" & "B".TABLE | | | #5 CALCULATION FOR THOSE CONDUCTORS IS | | | .3285 AREA SQ. IN. PLEASE INDICATE | | | CONDUIT TYPE BEING USED FOR FILL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL; | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|