Plan Review Notes
Plan Review Notes For Permit 02100787
Permit Number 02100787
Review Stop P
Sequence Number 2
Notes
Date Text
2002-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) SHTS P-1 AND P-2 FROM PREVIOUS RE-
 VIEW. ALL INDIRECT WASTE SHALL DRAIN IN-
 TO A FLOOR SINK. SEC 802.3 - SEE THE
 STEAMER, BOTH ICE BINS IN BAR AREA, AND
 CONDENSATE BY WATER HEATER.
 2) FOLLOWING ISSUES FOR GAS APPLICATION.
 FOLLOWING MANUFACTURE SHEETS NOT SUB-
 MITTED. STEAMER, CHEESE MELTER, ROTISS-
 ERIE, AND THE WATER HEATER.
 DISCREPENCIES BETWEET GAS RISER AND MAN-
 UFACTURE SHEETS. ***********
 CHARBROILER SHOWS 160K ON RISER - MANUF.
 SHEETS SHOW 195K.
 FRYERS SHOW (3) @ 122K ON RISER - MANUF.
 SHEETS SHOW 90K EACH.
 OVENS SHOW90K ON RISER - MANUF. SHEETS
 SHOW 88K.
 RANGE @ 230K NOT SHOWN ON RISER.
 PLEASE CLAIRFY. THIS SHALL AFFECT THE
 PIPE SIZING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377