| Plan Review Notes For Permit 02100787 |
| Permit Number |
02100787 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHTS P-1 AND P-2 FROM PREVIOUS RE- | | | VIEW. ALL INDIRECT WASTE SHALL DRAIN IN- | | | TO A FLOOR SINK. SEC 802.3 - SEE THE | | | STEAMER, BOTH ICE BINS IN BAR AREA, AND | | | CONDENSATE BY WATER HEATER. | | | 2) FOLLOWING ISSUES FOR GAS APPLICATION. | | | FOLLOWING MANUFACTURE SHEETS NOT SUB- | | | MITTED. STEAMER, CHEESE MELTER, ROTISS- | | | ERIE, AND THE WATER HEATER. | | | DISCREPENCIES BETWEET GAS RISER AND MAN- | | | UFACTURE SHEETS. *********** | | | CHARBROILER SHOWS 160K ON RISER - MANUF. | | | SHEETS SHOW 195K. | | | FRYERS SHOW (3) @ 122K ON RISER - MANUF. | | | SHEETS SHOW 90K EACH. | | | OVENS SHOW90K ON RISER - MANUF. SHEETS | | | SHOW 88K. | | | RANGE @ 230K NOT SHOWN ON RISER. | | | PLEASE CLAIRFY. THIS SHALL AFFECT THE | | | PIPE SIZING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|