| Plan Review Notes For Permit 02100787 |
| Permit Number |
02100787 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-05 00:00:00 | PLAN SHEETM-1 PLEASE SEE NOTE #1 | | | BELOW. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION, GAS, & WALK-IN COOLER/ | | | FREEZER.PROVIDE MANUFACTURER SUBMITTAL | | | DATA & INSTALLATION INSTRUCTIONS WITH | | | WALK-IN COOLER/FREEZER APPLICATION. | | | IF CONDENSERS ARE REMOTE TYPE, PROVIDE | | | SUBMITTAL ON COND UNIT STAND IF LOCATED | | | ON THE ROOF. | | | | | | HOOD PLAN REVIEW: | | | 1.PLAN SHEET M-1 INDICATES 2 SF #1 ON | | | THE PLAN & AIR BALANCE SCHEDULE.HOOD | | | DEPOT DWG 1 & 3 INDICATE SF #1 & 2, | | | PLEASE CORRECT PLAN SHEET M-1 TO REFLECT | | | WHAT IS SHOWN ON SHOP DWG. | | | PROVISO: | | | TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP | | | AIR & THE AIR IN THE CONDITIONED SPACE | | | SHALL NOT EXCEED 10 DEGREES F. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|