Plan Review Notes
Plan Review Notes For Permit 02100787
Permit Number 02100787
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-11-22 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD,DUCT, AND EXTINGUISHING
 SYSTEM.
  
 2) DIRECTIONAL ARROW ON EXIT SIGN
 NEAR STAIRWAY IS NOT NECESSARY.
  
 3) MANUAL PULL STATION AND HORN
 STROBE SHOULD BE RELOCATED AWAY FROM
 ENTRY HANDICAP RAMP.
  
 4) THE MANUAL PULL STATION IS NOT
 NEEDED NEAR THE WEST SIDE OF ENTRY
 HANDICAP RAMP. (HOSTESS AREA)
  
 5) THE HOOD SYSTEM EXHAUST SHALL BE A
 MINIMUM OF AT LEAST 40" ABOVE THE
 ROOF.
  
 6) PERMANANT PLATFORMS " SHALL BE OF
 MATERIALS REQUIRED FOR THE TYPE OF
 BUILDING CONSTRUCTION EXCEPT THE FLOOR
 FINISH MAY BE OF WOOD. IF THE SPACE
 BENEATH THE PLATFORM IS USED FOR STORAGE
 OR ANY OTHER PURPOSE OTHER THAN
 EQUIPMENT WIRING OR PLUMBING, THE FLOOR
 CONSTRUCTION SHALL NOT BE LESS THAN ONE
 HOUR". RE: NFPA 101, THE LIFE SAFETY
 CODE, NEW ASSEMBLY OCCUPANCIES.
  
 7) ALL STAIRS, RAMPS, AND HANDRAILS ARE
 TO COMPLY WITH THE FLORIDA BUILDING CODE
 AND THE FLORIDA FIRE PREVENTION CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910