| Plan Review Notes For Permit 02100787 |
| Permit Number |
02100787 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-11-22 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD,DUCT, AND EXTINGUISHING | | | SYSTEM. | | | | | | 2) DIRECTIONAL ARROW ON EXIT SIGN | | | NEAR STAIRWAY IS NOT NECESSARY. | | | | | | 3) MANUAL PULL STATION AND HORN | | | STROBE SHOULD BE RELOCATED AWAY FROM | | | ENTRY HANDICAP RAMP. | | | | | | 4) THE MANUAL PULL STATION IS NOT | | | NEEDED NEAR THE WEST SIDE OF ENTRY | | | HANDICAP RAMP. (HOSTESS AREA) | | | | | | 5) THE HOOD SYSTEM EXHAUST SHALL BE A | | | MINIMUM OF AT LEAST 40" ABOVE THE | | | ROOF. | | | | | | 6) PERMANANT PLATFORMS " SHALL BE OF | | | MATERIALS REQUIRED FOR THE TYPE OF | | | BUILDING CONSTRUCTION EXCEPT THE FLOOR | | | FINISH MAY BE OF WOOD. IF THE SPACE | | | BENEATH THE PLATFORM IS USED FOR STORAGE | | | OR ANY OTHER PURPOSE OTHER THAN | | | EQUIPMENT WIRING OR PLUMBING, THE FLOOR | | | CONSTRUCTION SHALL NOT BE LESS THAN ONE | | | HOUR". RE: NFPA 101, THE LIFE SAFETY | | | CODE, NEW ASSEMBLY OCCUPANCIES. | | | | | | 7) ALL STAIRS, RAMPS, AND HANDRAILS ARE | | | TO COMPLY WITH THE FLORIDA BUILDING CODE | | | AND THE FLORIDA FIRE PREVENTION CODE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|