Plan Review Notes
Plan Review Notes For Permit 02100787
Permit Number 02100787
Review Stop B
Sequence Number 2
Notes
Date Text
2002-12-12 00:00:00SECOND REVIEW
  
 FBC 11-5.4 REQUIRES "ALL" DINING AREAS
 TO BE ACCESSIBLE, NOT JUST THE ONE
 DESIGNATED AREA SHOWN ON THE PLANS
 DATED 11/17/02 SHEET A1.PLEASE REVISE
 AS NECESSARY.SEE ALSO FBC
 11-4.1.6(1)(A).
  
 FBC 1003.2.7 REQUIRES CHANGES OF LEVEL
 IN THE MEANS OF EGRESS OF 12" OR LESS
 TO BE BY RAMP.SEVERAL LOCATIONS ON
 THE PLAN INDICATE 12" AND 6" CHANGES.
 PLEASE REVISE AS NECESSARY.
  
 PLEASE PROVIDE OR SPECIFY THAT THE EIFS
 TRIM SHOWN IN SECTION 1/A5 MEETS FBC
 CLASS "C" AS NOTED ON FBC 803.2 FOR THE
 INTENDED SIZES, SHAPES AND QUANTITIES.