| Plan Review Notes For Permit 02100787 |
| Permit Number |
02100787 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-12-12 00:00:00 | SECOND REVIEW | | | | | | FBC 11-5.4 REQUIRES "ALL" DINING AREAS | | | TO BE ACCESSIBLE, NOT JUST THE ONE | | | DESIGNATED AREA SHOWN ON THE PLANS | | | DATED 11/17/02 SHEET A1.PLEASE REVISE | | | AS NECESSARY.SEE ALSO FBC | | | 11-4.1.6(1)(A). | | | | | | FBC 1003.2.7 REQUIRES CHANGES OF LEVEL | | | IN THE MEANS OF EGRESS OF 12" OR LESS | | | TO BE BY RAMP.SEVERAL LOCATIONS ON | | | THE PLAN INDICATE 12" AND 6" CHANGES. | | | PLEASE REVISE AS NECESSARY. | | | | | | PLEASE PROVIDE OR SPECIFY THAT THE EIFS | | | TRIM SHOWN IN SECTION 1/A5 MEETS FBC | | | CLASS "C" AS NOTED ON FBC 803.2 FOR THE | | | INTENDED SIZES, SHAPES AND QUANTITIES. |
|