| 2002-11-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN- |
| | ESS REGULATION, HOTEL AND RESTAURANT DIV |
| | 2) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| | MUM FACILITIES PER TABLE 1003.1 BLDG. |
| | CODE AND TABLE 403.1 PLUMBING CODE. IN- |
| | DICATE IF SEATING IS FIXED OR NOT. |
| | 3) SHT D-1 ALL CAPPED OFF PLUMBING SHALL |
| | BE INSPECTED PRIOR TO COVERING. |
| | 4) SHT P-1 PLUMBING NOTES #16, AIR CHAM- |
| | BERS ARE NOT APPROVED. WATER HAMMER ARR- |
| | ESTORS REQUIRED BY SECTION 604.9 SHALL |
| | BE LOCATED NEAR THE FIXTURE IN AN "EFF- |
| | ECTIVE RANGE" NOT AT TOP OF DROP IN |
| | CEILING PER MANUFACTURE INSTALLATION IN- |
| | STRUCTIONS AND PDI-WH 201. |
| | 5) RPZ BACKFLOW IS REQUIRED ON WATER |
| | SERVICE IN SPACE LOCATED MAXIMUM OF 4' |
| | AFF FOR SERVICING AND TESTING. |
| | 6) SHTS P-1/P-3 FOOD PREP SINK, #56, |
| | SHALL BE DRAINED INDIRECTLY INTO A FLOOR |
| | SINK PER SECTION 802.1.1 |
| | 7) SHTS P-1/P-3 ALL INDIRECT WASTE SHALL |
| | BE DRAINED INTO A FLOOR SINK PER SECTION |
| | 802.3. SAFE WASTES AND HUB DRAINS ARE |
| | NOT APPROVED. |
| | 8) SHTS P-1/P-3 DISHWASHER SHALL DRAIN |
| | TO SANITARY NOT GREASE WASTE PER UTILITY |
| | DEPT. |
| | 9) SHT P-2 INDICATE TEMPERATURE OF WATER |
| | FROM WATER HEATER. 110 DEGREE MAXIMUM |
| | TEMP. FOR HAND SINKS. |
| | 10) SHT P-3 FLOOR DRAIN SHOWN ON SHT P-1 |
| | NOT SHOWN ON SANT. RISER DIAGRAM. |
| | 11) SHT A-1 DOORS SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE OF ANY FIXTURE. |
| | SECTION 11-4.17.5. SEE MEN'S/WOMEN'S |
| | STALLS IN RESTROOMS |
| | 12) SHT P-3 GAS PIPING NOTES #1, CODE |
| | IN USE FBC-2001 FUEL GAS, NOT STANDARD |
| | GAS CODE. PLEASE CHANGE REFERENCE. |
| | 13) SHT P-3 GAS RISER DIAGRAM, TOTAL |
| | DEVELOPED LENGTH IS APPROX 150' NOT 137' |
| | AS SHOWN. PLEASE ADJUST PIPE SIZES NOTED |
| | IN RED ON PLANS AND CHANGE ACCORDINGLY. |
| | 14) TYPE OF GAS, (LP OR NATURAL) |
| | 15)SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE SEC. 402.2 |
| | 16) SHT P-3 GAS RISER DIAGRAM, UNION RE- |
| | QUIRED BETWEEN MANUAL SHUT OFF VALVE AND |
| | AUTOMATIC SHUT OFF VALVE. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |