Plan Review Notes
Plan Review Notes For Permit 02100787
Permit Number 02100787
Review Stop P
Sequence Number 1
Notes
Date Text
2002-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) PLEASE ROUTE PLANS TO DEPT OF BUSIN-
 ESS REGULATION, HOTEL AND RESTAURANT DIV
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES PER TABLE 1003.1 BLDG.
 CODE AND TABLE 403.1 PLUMBING CODE. IN-
 DICATE IF SEATING IS FIXED OR NOT.
 3) SHT D-1 ALL CAPPED OFF PLUMBING SHALL
 BE INSPECTED PRIOR TO COVERING.
 4) SHT P-1 PLUMBING NOTES #16, AIR CHAM-
 BERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE LOCATED NEAR THE FIXTURE IN AN "EFF-
 ECTIVE RANGE" NOT AT TOP OF DROP IN
 CEILING PER MANUFACTURE INSTALLATION IN-
 STRUCTIONS AND PDI-WH 201.
 5) RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE IN SPACE LOCATED MAXIMUM OF 4'
 AFF FOR SERVICING AND TESTING.
 6) SHTS P-1/P-3 FOOD PREP SINK, #56,
 SHALL BE DRAINED INDIRECTLY INTO A FLOOR
 SINK PER SECTION 802.1.1
 7) SHTS P-1/P-3 ALL INDIRECT WASTE SHALL
 BE DRAINED INTO A FLOOR SINK PER SECTION
 802.3. SAFE WASTES AND HUB DRAINS ARE
 NOT APPROVED.
 8) SHTS P-1/P-3 DISHWASHER SHALL DRAIN
 TO SANITARY NOT GREASE WASTE PER UTILITY
 DEPT.
 9) SHT P-2 INDICATE TEMPERATURE OF WATER
 FROM WATER HEATER. 110 DEGREE MAXIMUM
 TEMP. FOR HAND SINKS.
 10) SHT P-3 FLOOR DRAIN SHOWN ON SHT P-1
 NOT SHOWN ON SANT. RISER DIAGRAM.
 11) SHT A-1 DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY FIXTURE.
 SECTION 11-4.17.5. SEE MEN'S/WOMEN'S
 STALLS IN RESTROOMS
 12) SHT P-3 GAS PIPING NOTES #1, CODE
 IN USE FBC-2001 FUEL GAS, NOT STANDARD
 GAS CODE. PLEASE CHANGE REFERENCE.
 13) SHT P-3 GAS RISER DIAGRAM, TOTAL
 DEVELOPED LENGTH IS APPROX 150' NOT 137'
 AS SHOWN. PLEASE ADJUST PIPE SIZES NOTED
 IN RED ON PLANS AND CHANGE ACCORDINGLY.
 14) TYPE OF GAS, (LP OR NATURAL)
 15)SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 16) SHT P-3 GAS RISER DIAGRAM, UNION RE-
 QUIRED BETWEEN MANUAL SHUT OFF VALVE AND
 AUTOMATIC SHUT OFF VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377