Plan Review Notes
Plan Review Notes For Permit 02100787
Permit Number 02100787
Review Stop M
Sequence Number 1
Notes
Date Text
2002-10-30 00:00:00HVAC PLANS SUBMITTED ARE CODE COMPLIANT.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLER/FREEZER
  
 WALK-IN COOLERS & FREEZERS -
 PLEASE PROVIDE MANUFACTURER SUBMITTAL &
 INSTALLATION INSTRUCTIONS.INDICATE ON
 PLANS IF COOLERS ARE SELF CONTAINED OR
 HAVE A REMOTE CONDENSER.SHOULD
 CONDENSER BE REMOTE PROVIDE DETAIL OF
 STAND SHOWING COMPLIANCE WITH 2001 FBC
 1511.7 (MINIMUM CLEARANCE BETWEEN THE
 ROOF SURFACE & BOTTOM OF THE SUPPORT
 RAIL).
  
 HOOD & GREASE DUCT -
 SHOW COMPLIANCE WITH 2001 FBC(M) 506
 THRU 508 - GREASE DUCT, HOOD & MAKE UP
 AIR.PLEASE NOTE TERMINATION OF GREASE
 DUCT ABOVE THE ROOF SHALL BE A MINIMUM
 40" ABOVE THE ROOF SURFACE AS PER NFPA
 96.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.