| Plan Review Notes For Permit 02100787 |
| Permit Number |
02100787 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-30 00:00:00 | HVAC PLANS SUBMITTED ARE CODE COMPLIANT. | | | | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPRESSION & WALK-IN COOLER/FREEZER | | | | | | WALK-IN COOLERS & FREEZERS - | | | PLEASE PROVIDE MANUFACTURER SUBMITTAL & | | | INSTALLATION INSTRUCTIONS.INDICATE ON | | | PLANS IF COOLERS ARE SELF CONTAINED OR | | | HAVE A REMOTE CONDENSER.SHOULD | | | CONDENSER BE REMOTE PROVIDE DETAIL OF | | | STAND SHOWING COMPLIANCE WITH 2001 FBC | | | 1511.7 (MINIMUM CLEARANCE BETWEEN THE | | | ROOF SURFACE & BOTTOM OF THE SUPPORT | | | RAIL). | | | | | | HOOD & GREASE DUCT - | | | SHOW COMPLIANCE WITH 2001 FBC(M) 506 | | | THRU 508 - GREASE DUCT, HOOD & MAKE UP | | | AIR.PLEASE NOTE TERMINATION OF GREASE | | | DUCT ABOVE THE ROOF SHALL BE A MINIMUM | | | 40" ABOVE THE ROOF SURFACE AS PER NFPA | | | 96. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|