| Notes |
| Date |
Text |
| 2002-10-31 00:00:00 | 1) PLEASE PROVIDE A LIFE SAFETY PLAN | | | TO THIS OFFICE FOR THE STEAKHOUSE. | | | | | | 2) PLEASE INDICATE INTERIOR | | | CLASSIFICATION FOR THE WALLS AND | | | CEILINGS. | | | | | | 3) PLEASE INDICATE WHERE HANDICAPPED | | | SEATING EXISTS. | | | | | | 4) THE EXISTING HARDWARE ON THE EXISTING | | | DOOR MUST HAVE PANIC HARDWARE. | | | | | | 5) PLANS INDICATE A FIRE ALARM PANEL | | | INSIDE STEAKHOUSE. NO NEW FIRE ALARM | | | PANELS ARE ALLOWED TO BE INSTALLED IN | | | ANY TENANT SPACE. ALL FIRE ALARM DEVICES | | | MUST BE CONNECTED TO THE EXISTING BASE | | | BUILDING SYSTEMS. PLEASE REVISE PLANS. | | | | | | 6) IS THERE ANY WAITING SPACES WITHIN | | | TENANT SPACE. IF SO, WHAT ARE YOU | | | USING FOR SQUARE FOOTAGE PER PERSON. | | | | | | 7) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE INSTALLATION OF ANY NEW HOODS. | | | DUCTS, OR SUPPRESSION SYSTEMS. | | | | | | 8) NO INFORMATION PROVIDED WITH REGARDS | | | TO THE FIRE SPRINKLER SYSTEM. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|