| Plan Review Notes For Permit 02100787 |
| Permit Number |
02100787 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-11-05 00:00:00 | **************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE, PLANS ARE REQ`D | | | TO BE DONE BY A PE. UNDER FS/FAC. | | | 471.003(2)(H)1/ FBC 104.4.1.3, FAC | | | 553-79(6)A. | | | | | | 2)NOTE: PLEASE CLARIFY CIRCUTIING FOR | | | EM LTS AND EXIT LTS. 700-12 | | | | | | 3)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | GRROUND BETWEEN PANEL AND TRANSFORMERTS | | | SIZE 250--122 | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS, | | | PER 220-3,220-310, 220-20,220-11, | | | 220-13.215-3/230-42 | | | | | | 5)NOTE: PLEASE NOTE ON PLANS, FEEDER | | | COLORS PER LOCALAMENDMENTS 215-5 | | | BROWN/PURPL/YELLOW. | | | | | | 6)NOTE: PLEASE SHOW GROUNDING FOR | | | TRANSFORMER. PER 250-30 | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | 110-9/215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|