Plan Review Notes
Plan Review Notes For Permit 02100741
Permit Number 02100741
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-28 00:00:00************ NOTES / PROVISO *********
  
 1)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 2)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE
 RECEPTS PER 210-52C-1
  
 3)NOTE: PLEASE NOTE MISSING HALLWAY
 RECEPTS PER 210-52H
  
 4)NOTE : PLEASE NOTE OUTLET SPACING PER
 210-52
  
 5)NOTE: PLEASE NOTE PANEL SCHEUDULE
 SHOWS ONE CENTRAL A/C SYSTEM AND PLANS
 SHOW TWO? PLEASE CORRELATE.
  
 PLEASE NOTE, PLANS NEED TO BE REVISED
 BEFORE ROUGH ELECTRICAL INSPECTION IS
 CALLED IN.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved