| Plan Review Notes For Permit 02100723 |
| Permit Number |
02100723 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-28 00:00:00 | *********** NOTES/PROVISO********** | | | | | | 1)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL. SIZE PER 250-122. | | | | | | 2)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE | | | OUTLETS PER 210-52C-1 | | | | | | 3)NOTE: PLEASE NOTE MISSING OUTLETS PER | | | 210-52H | | | | | | 4)NOTE: PLEASE NOTE MISSING OUTLETS PER | | | 210-52 | | | | | | 5)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS | | | ONLY ONE CENTRAL A/C SYSTEM AND PLANS | | | SHOW TWO? PLEASE CORRELATE. | | | | | | PLEASE NOTE, PLANS NEED TO BE REVISED | | | AND SUBMITTED FOR REVIEW BEFORE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|