2002-10-28 00:00:00*********** NOTES/PROVISO**********
  
 1)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122.
  
 2)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE
 OUTLETS PER 210-52C-1
  
 3)NOTE: PLEASE NOTE MISSING OUTLETS PER
 210-52H
  
 4)NOTE: PLEASE NOTE MISSING OUTLETS PER
 210-52
  
 5)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS
 ONLY ONE CENTRAL A/C SYSTEM AND PLANS
 SHOW TWO? PLEASE CORRELATE.
  
 PLEASE NOTE, PLANS NEED TO BE REVISED
 AND SUBMITTED FOR REVIEW BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  