Plan Review Notes
Plan Review Notes For Permit 02100717
Permit Number 02100717
Review Stop E
Sequence Number 1
Notes
Date Text
2002-10-28 00:00:00************** NOTES/ PROVISO *********
  
 1)NOTE PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. SIZE PER 250-122
  
 2)NOTE: PLEASE NOTE MISSING HALLWAY RECP
 PER 210-52H
  
 3)NOTE; PLEASE NOTE OUTLET SPACING PER
 210-52
  
 4)NOTE: PLEASE NOTE KITCHEN COUNTERSPACE
 RECEPTS TO MEET 210-52C-1
  
 5)NOTE: PLEASE NOTE PANEL SCHEDULES SHOW
 ONE A/C SYSTEM AND PLANS SHOW TWO?
 PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372