| Plan Review Notes For Permit 02100716 |
| Permit Number |
02100716 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-10-28 00:00:00 | ************ NOTES/ REDLINED ******** | | | | | | 1)NOTE: PLEASE NOTE MISSING RECEPTS | | | PER 210-52 | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN MAIN AND | | | PANEL. SIZE PER 250-122 | | | | | | 3)NOTE: PLEASE NOTE HALLWAY RECEPT PER | | | 210-52 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|