2002-11-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA-AMEND 98 DESIGN MANUAL
  
 1) SHTS A-U1 & A-U2, INDICATE ON PLANS
 SPECIFICATION "A" OR "B" FOR BATHROOMS
 PER REQUIREMENT 7B PAGE 7.35 DESIGN
 MANUAL FHA-98
 2) SHT ADT-II BACKING FOR W/C'S AND TUBS
 TO BE ACCORDING TO REQUIREMENT 6 PAGE
 6.9 DESIGN MANUAL FHA-98.
 3) SHT ADT-II THE TOP OF LAV FIXTURE RIM
 IS A MAXIMUM OF 2'10" ABOVE FINISHED
 FLOOR. PLEASE INDICATED ON BATHROOM DE-
 TAIL.
 4) SHT P-U2 DOMESTIC WATER RISER, LOCATE
 WATER HAMMER ARRESTOR AT WASH MACHINE
 NEAR FIXTURE NOT AT TOP OF DROP.
 5) SHT P-D1 PLUMBING GENERAL NOTES #6,
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 USAGE. PLEASE DELETE REFERENCE.
 6) SHT PD-1 WATER HEATER DETAIL, THE
 RELIEF VALVE DISCHARGE PIPE SHALL NOT
 HAVE ANY TRAPPED SECTIONS. SEC 504.7.1
 THERMAL EXPANSION CONTROL IS ALSO RE-
 QUIRED. SECTION 607.3.2.
  