| 2002-11-05 00:00:00 | DENIED:TYPE V |
| | |
| | PLEASE CLARIFY THE FOLLOWING INFORMATION |
| | |
| | 1.NOTES CONCERNING THE DRYER & TOILET |
| | EXHAUST ARE NOT CLEAR.PLAN SHEET |
| | A-DT1 SHOWS A 1 HR SHAFT DETAIL FOR |
| | THE TOILET & DRYER EXHAUST, PLAN |
| | SHEET AC-D1 ON THE EXHAUST DUCT |
| | DETAIL SHOWS ONLY A 1 HR FIRE RATED |
| | CAULK SEALANT WITHOUT INDICATING THE |
| | 1 HR SHAFT. |
| | |
| | PLEASE PROVIDE A RISER DETAIL |
| | SHOWING WHERE THE SHAFT BEGINS & |
| | ENDS.REFERENCE PLAN SHEET A-DT1, |
| | (SHAFT DETAIL) ON THE MECHANICAL |
| | PLAN. |
| | |
| | 2.PLAN SHEET AC-D1 - NOTE #2, STATES |
| | DRYER EXHAUST DISCHARGE ON ROOF |
| | SHALL BE SIMILAR TO TOILET EXHAUST |
| | DISCHARGE BUT SHALL NOT BE SCREENED. |
| | AS PER 2001 FBC(M) 504.4, SHALL |
| | TERMINATE ON THE OUTSIDE OF THE |
| | BUILDING & SHALL BE EQUIPPED WITH A |
| | BACKDRAFT DAMPER. |
| | |
| | 3.PROVIDE OUTSIDE AIR CALCULATIONS IN |
| | ACCORDANCE WITH 2001 FBC(M) 402.2 |
| | FOR NATURAL VENTILATION OR TABLE |
| | 403.3.PROVIDE CALCULATIONS. |
| | |