2002-11-06 00:00:00*********** UNSAT ****************
  
  
  
  
 1)NOTE: PLEASE NOTE ON PLANS, A DISC
 MAY BE REQ`D FOR AHU/WATER HEATER UNLESS
 LOCK OF DEVICE IS APPROVED BY THE CITY
 OF WEST PALM BEACH. THERE ARE MANY "LOCK
 OFF " DEVICES THAT ARE NOT ACCEPTABLE.
 90-4
  
 2)NOTE: PLEASE CALRIFY HOW 12KW AT 70%
 IS = TO 5.6KW?
  
 3)NOTE: PLEASE CLARIFY RECEPTS FOR A/C
 COND UNITS.210-63
  
 4)NOTE: PLEASE LIST OR NOTE MAINS AT
 METER LOCATION ON E-T5.3
  
 5)NOTE: PLEASE CLARIFY EQUIPMENT GROND-
 -ING BETWEEN MAIN AND H PANEL.
 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372