| 2002-11-12 00:00:00 | PAID PLAN REVIEW ONLY, NOT A PERMIT |
| | APPLICATION. |
| | |
| | THE MINIMUM CONSTRUCTION TYPE IS TYPE |
| | VI, ONE HOUR PROTECTED. |
| | |
| | THE PERMIT PLANS MUST HAVE A FIRE |
| | SPRINKLER SYSTEM AS REQUIRED BY FBC |
| | 903.8 SHOWN ON THE PLANS. |
| | |
| | TWO INDEPENDENT EXITS ARE REQUIRED FROM |
| | THE THIRD FLOOR AND THE STAIRS ARE |
| | REQUIRED TO BE ENCLOSED IN FIRE RATED |
| | CONSTRUCTION FBC 1006.1, OR COMPLY WITH |
| | FBC 1006.2 FOR EXTERIOR STAIRS. |
| | |
| | SHEET A-T5.2 CALLS FOR ROOF COVERINGS |
| | MEETING THE REQUIREMENTS OF FBC 3207. |
| | THIS SHOULD BE REVISED TO FBC 1503. |
| | PLEASE BE AWARE THAT CITING CODE |
| | SECTIONS IS NOT AN ACCEPTIBLE |
| | SUBSTITUTE FOR SPECIFIC DESIGN |
| | INFORMATION.SEE FBC 104.2.1. |
| | |
| | SHEET AT 4.2 HAS NOTES FOR ROOF TILE |
| | NAILINGS THAT ARE INCONSISTENT WITH THE |
| | SEVERAL NOTICE OF ACCEPTANCE REPORTS. |
| | |
| | SHEET AT4.2 HAS SEVERAL DECLARATIONS FOR |
| | THE ATTIC VENTILATION THAT WOULD |
| | REQUIRE THE SCREEN VENTS TO HAVE OPEN |
| | AREA ON THE ORDER OF 80% WHICH WOULD BE |
| | AN UNUSUAL SCREEN. |
| | |
| | IF PRODUCT APPROVALS FOR THE DOORS, |
| | WINDOWS AND ROOF COVERINGS ARE NOT |
| | INCLUDED AT THE TIME OF PERMIT |
| | APPLICATION, SEPARATE PLANS PERMITS AND |
| | FEES WILL BE REQUIRED FOR THAT WORK. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY, THE PERMIT PLANS |
| | STAMPED BY THAT OFFICE AND A COPY OF |
| | THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. CALL 561-233-5025 FOR MORE |
| | INFORMATION. |