Plan Review Notes For Permit 02100712
Permit Number 02100712
Review Stop M
Sequence Number 7
Notes
Date Text
2003-11-18 00:00:00PLEASE NOTE PLAN SHEET AC-DT2 IS DENIED.
 PLAN OMITTED DETAIL OF SHAFT FOR THE
 REFRIGERATION LINES.AS PER ASHRAE
 15-92 SECTION 11.12.3 REFRIGERANT PIPING
 SHALL NOT BE INSTALLED VERTICALLY
 THROUGH FLOORS FROM ONE STORY TO ANOTHER
 EXCEPT AS FOLLOWS:
 (B) IN APPROVED RIGID, TIGHT AND
 CONTINUOUS FIRE-RESISTING PIPE DUCT OR
 SHAFT. ON THE OTHER WALL OF THE BUILDING
 (NOT IN AIR SHAFT OR CLOSED COURT).THE
 SHAFT SHALL BE VENTED TO THE OUTSIDE OR
 TO THE SPACE SERVED BY THE SYSTEM.
  