| 2002-11-05 00:00:00 | DENIED: TYPE IV |
| | |
| | PLEASE CLARIFY THE FOLLOWING INFORMATION |
| | |
| | 1.NOTES CONCERNING THE DRYER & TOILET |
| | EXHASUT ARE NOT CLEAR.PLAN SHEET |
| | AC-U3 NOTE INDICATES SHAFT TO START |
| | AT THE 2ND FLOOR AT THE ELECTRICAL |
| | CLOSET?DETAIL ON PLAN SHEET AC-D1 |
| | INDICATES A 1 HR RATE CAULK.PLAN |
| | SHEET A-DT1 SHOWS A 1 HR SHAFT |
| | DETAIL FOR THE TOILET & DRYER |
| | EXHAUST. |
| | |
| | PLEASE PROVIDE A RISER DETAIL |
| | SHOWING WHERE THE SHAFT DEGINS & |
| | ENDS.REFERENCE PLAN SHEET A-DT1, |
| | (SHAFT DETAIL) ON THE MECHANICAL |
| | PLAN. |
| | |
| | 2.PLAN SHEET AC-D1 - NOTE #2 STATES, |
| | DRYER EXHAUST DISCHARGE ON ROOF |
| | SHALL BE SIMILAR TO TOILET EXHAUST |
| | DISCHARGE BUT SHALL NOT BE SCREENED. |
| | AS PER 2001 FBC(M) 504.4, SHALL |
| | TERMINATE OUTSIDE OF THE BUILDING |
| | & SHALL BE EQUIPPED WITH A BACKDRAFT |
| | DAMPER. |
| | |
| | 3.PROVIDE OUTSIDE AIR CALCULATIONS IN |
| | ACCORDANCE WITH 2001 FBC(M) 402.2 |
| | FOR NATURAL VENTILATION OR TABLE |
| | 403.3.PROVIDE CALCULATIONS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |