| Notes |
| Date |
Text |
| 2002-11-06 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE MISSING HALLWAY | | | OUTLET E-U3. 210-52H | | | | | | 2)NOTE: PLEASE NOTE, A DISC MAY BE REQ`D | | | FOR AHU/WATER HEATERS.NOT ALL LOCK-OFF | | | DEVICES ARE APPROVED BY THE CITY OF | | | WEST PALM BEACH. AHJ. PLEASE NOTE. | | | | | | | | | 3)NOTE: PLEASE CLAROFY HOW 12KW FOR | | | RANGE AT 70% BECOMES 5.6KW? | | | | | | 4)NOTE: PLEASE CLARIFY RECEPT FOR A/C | | | COND UNITS. 210-63 | | | | | | 5)NOTE: PLEASE NOTE/SHOW HEIGHT REQ`- | | | -MENTS PER FHAR 24CFR 100.205 ON PLANS. | | | | | | 6)NOTE: PLEASE NOTE FEEDER SIZES NEED TO | | | BE SIZED PER 310-16/ 75 DEGREE COLUMN. | | | 110-14. | | | | | | 7)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | -ING BETWEEN MAIN AND H PANEL. | | | 250-122 | | | | | | 8)NOTE: PLEASE INDICATE MAINS ON METER | | | BANK ON E-T4.3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|