Plan Review Notes
Plan Review Notes For Permit 02100712
Permit Number 02100712
Review Stop E
Sequence Number 1
Notes
Date Text
2002-11-06 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SEE MISSING HALLWAY
 OUTLET E-U3. 210-52H
  
 2)NOTE: PLEASE NOTE, A DISC MAY BE REQ`D
 FOR AHU/WATER HEATERS.NOT ALL LOCK-OFF
 DEVICES ARE APPROVED BY THE CITY OF
 WEST PALM BEACH. AHJ. PLEASE NOTE.
  
  
 3)NOTE: PLEASE CLAROFY HOW 12KW FOR
 RANGE AT 70% BECOMES 5.6KW?
  
 4)NOTE: PLEASE CLARIFY RECEPT FOR A/C
 COND UNITS. 210-63
  
 5)NOTE: PLEASE NOTE/SHOW HEIGHT REQ`-
 -MENTS PER FHAR 24CFR 100.205 ON PLANS.
  
 6)NOTE: PLEASE NOTE FEEDER SIZES NEED TO
 BE SIZED PER 310-16/ 75 DEGREE COLUMN.
 110-14.
  
 7)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 -ING BETWEEN MAIN AND H PANEL.
 250-122
  
 8)NOTE: PLEASE INDICATE MAINS ON METER
 BANK ON E-T4.3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372