| Plan Review Notes For Permit 02100711 |
| Permit Number |
02100711 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2003-11-18 00:00:00 | PLEASE NOTE PLAN SHEET AC-DT2 IS DENIED | | | PLAN OMITTED DETAIL OF SHAFT FOR THE | | | REFRIGERATION LINES.AS PER ASHRAE | | | 15-92 SECTION 11.12.3 REFRIGERANT PIPING | | | SHALL NOT BE INSTALLED VERTICALLY | | | THROUGH FLOORS FROM ONE STORY TO ANOTHER | | | EXCEPT AS FOLLOWS: | | | (B) IN APPROVED RIGID, TIGHT AND | | | CONTINUOUS FIRE-RESISTING PIPE DUCT OR | | | SHAFT. ON THE OUTER WALL OF THE BUILDING | | | (NOT IN AIR SHAFT OR CLOSED COURT).THE | | | SHAFT SHALL BE VENTED TO THE OUTSIDE | | | OR TO THE SPACE SERVED BY THE SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW | | | NOTES. PLEASE CORRELATE PLANS/PAPERWORK | | | FOR COTTAGES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|